Hitachi Virtual Storage Platform G700 88-02-0x Hardware Reference Guide This document provides information about the system hardware components and the mechanical and environmental specifications for the Hitachi Virtual Storage Platform G700 storage system. MK-97HM85013-01 September 2018...
Page 2
Materials. “Materials” mean text, data, photographs, graphics, audio, video and documents. Hitachi reserves the right to make changes to this Material at any time without notice and assumes no responsibility for its use. The Materials contain the most current information available at the time of publication.
Preface This guide describes the hardware features and specifications of the Hitachi Virtual Storage Platform G700. Intended audience This document is intended for Hitachi Vantara representatives, system administrators, and authorized service providers who install, configure, and operate the VSP Gx00 models.
Read the release notes before installing and using this product. They may contain requirements or restrictions that are not fully described in this document or updates or corrections to this document. Release notes are available on Hitachi Vantara Support Connect: https://knowledge.hitachivantara.com/Documents.
Page 9
Indicates required or expected values. Example: { a | b } indicates that you must choose either a or b. | vertical bar Indicates that you have a choice between two or more options or arguments. Examples: Preface Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
1,000 TB or 1,000 bytes 1 exabyte (EB) 1,000 PB or 1,000 bytes Logical capacity values (for example, logical device capacity, cache memory capacity) are calculated based on the following values: Preface Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Getting help Hitachi Vantara Support Connect is the destination for technical support of products and solutions sold by Hitachi Vantara. To contact technical support, log on to Hitachi Vantara Support Connect for contact information: https://support.hitachivantara.com/en_us/ contact-us.html. Hitachi Vantara Community is a global online community for Hitachi Vantara customers, partners, independent software vendors, employees, and prospects.
Please send us your comments on this document to doc.comments@hitachivantara.com. Include the document title and number, including the revision level (for example, -07), and refer to specific sections and paragraphs whenever possible. All comments become the property of Hitachi Vantara Corporation. Thank you! Preface...
Chapter 1: Overview The Hitachi Virtual Storage Platform G700 is a versatile modular, rack-mountable hybrid array storage system equipped with drive boxes, supporting SAS drives, flash drives, and TLC-NAND flash module drives, scaled for various storage capacity configurations. The storage systems provide high performance operations by using dual controllers with high-speed processors, dual in-line cache memory modules (DIMMs), cache flash memory (CFM), battery, fans and ports to connect iSCSI and Fibre Channel I/O modules.
Page 14
Flash drive tray (DBF): Up to 12 flash module drives (FMD) can be installed (2U size) ■ Supports system environments with mixed operating systems such as UNIX, Linux, ■ Windows, and VMware Chapter 1: Overview Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Each controller includes the following internal components such as a processor, dual in- line cache memory modules (DIMMs), cache flash memory (CFM), battery, and fans. The controller has an Ethernet connection for out-of-band management using Hitachi Device Manager - Storage Navigator. If the data path through one controller fails, all drives remain available to data hosts using a redundant data path through the other controller.
Page 16
ALARM LED Off: Normal operation. Red: Processor failure (system might be down). For assistance, contact customer support: https:// support.hitachivantara.com /en_us/contact-us.html. POWER ON/OFF (main Powers the storage system. switch) Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
(SIM) are issued: 452xxx, 462xxx, 3077xx, 4100xx, and 410100. Controllers Controller 1 (bottom) and Controller 2 (top). Backup module Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 18
Blink red one time: Main battery failure. Blink red two times: Backup battery failure. Blink red three times: Both batteries failed or preventive maintenance replacement of batteries can run. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Back end module LAN blade CBL controller power supply unit LEDs and connectors The following table lists the definitions of the CBL controller power supply unit LEDs and connectors. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Front end modules The following front end modules are available for the controllers. The LEDs display the operating status of the module. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Blue: Normal link status. Blink blue: Front end module is in communication status. ISCSI connectors Connect to Ethernet cables. 10-Gbps iSCSI board LEDs and connectors (copper) Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 22
Off: No link connection. PORT LED Green: Link connection is established. Blinking: Communication is in progress. Off: No link connection or not ready to communicate. ISCSI connectors Connect to Ethernet cables. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Item Description Fibre Channel connectors Connect to Fibre Channel cables. STATUS LED Green: Front end module is in power-on state. Red: Front end module can be removed safely. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 24
8-Gbps, 16-Gbps, or 32-Gbps Fibre Channel ports (left to right) CHB number Port 1 Port 2 Port 3 Port 4 CHB-1A CHB-1B CHB-1C CHB-1D CHB-1E CHB-1F CHB-1G CHB-1H CHB-2A CHB-2B CHB-2C CHB-2D CHB-2E CHB-2F CHB-2G Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Red: Small form-factor pluggable can be removed. Blue: Normal link status at 16-Gbps. Green: Normal link status at 4-Gbps or 8-Gbps. Fibre Channel connectors Connect to Fibre Channel cables. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
CHB-1E CHB-1F CHB-1G CHB-1H CHB-2A CHB-2B CHB-2C CHB-2D CHB-2E CHB-2F CHB-2G CHB-2H Back-end module LEDs and connectors The back-end module LEDs display the operating status of the module. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 27
Red: Back end module can be removed safely. PORT LED Blue: Link status is normal. PATH 0 connector Connect to a drive tray. PATH 1 connector Connects to a drive tray. Chapter 2: System controller Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
2U (88.2 mm) 2.5 inch (SFF) SFF with front panel bezel Number Item Description POWER LED Green: Drive tray is powered on. READY LED Green: Drive tray is operational. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Can be turned on or ■ turned off by the maintenance utility. ALM LED Red: Drive stopped due to a failure and can be replaced. ACT LED Green: Normal operation. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
ALARM LED Red: ENC can be replaced. PATH (IN) LED Blue: IN side port is linked PATH (IN) connector Connects to a controller or drive tray. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
LEDs to display its operating status. Number Item Description RDY LED Green: Normal operation. ACI IN LED Green: AC input is operating normally. ALM LED Red: Power supply unit can be replaced. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
■ the chassis. Can be turned on or ■ turned off by the maintenance utility. Lock Locks and unlocks the front panel bezel by using the supplied key. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Red: Drive stopped due to a failure and can be replaced. Large form-factor drives The twelve 3.5-inch large form factor drives are positioned horizontally. The slots are organized in the following order: Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Connects to the power cable provided with the storage system. AC IN LED Green: Normal operation. ALM LED Red: Power supply unit can be replaced. RDY LED Green: Normal operation. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
The following describes the physical specifications of the flash module drive tray. Number of Name Model name Height drive slots Drive type DW-F800-DBF 2U (87 mm) Flash module drive (FMD) FMD with front panel bezel Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Locks and unlocks the front panel bezel by using the supplied key. FMD front panel without bezel Number Item Description 1, 2 ACT LED Green: Normal operation. Blink: Drive is being accessed. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Receptacle Connects to the power cable provided with the storage system. Three LEDS, top to bottom: Green: Power supply unit is operating normally. RDY LED AC IN LED Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
3.5 inch (LFF) DB60C Dense intermix drive tray with front panel bezel Number Item Description POWER LED Green: Drive tray is powered on. READY LED Green: Drive tray is operational. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Dense intermix drive tray display LEDs Number Item Description Green: Normal operation. Blink: Drive is being accessed. ALM LED Red: Drive stopped due to a failure and can be replaced. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Connects to the power cable provided with the storage system. PATH (OUT) LED Blue: OUT side port is linked up. PATH (OUT) connector Connects to a drive tray. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 42
Indicates the location of ■ the chassis. Can be turned on or ■ turned off by the maintenance utility. POWER LED Green: ENC is in the power- on state. Chapter 3: Drive trays Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
The SVP is also available as a 64-bit software application provided by Hitachi Vantara. For the latest interoperability updates and details, see the SVP (Service Processor) OS and Hypervisor support for Gx00, Fx00 report at https://support.hitachivantara.com/en_us/...
<model number><system serial number>/emergency.do. For example: Storage system model Storage system serial number number 8320004 456789 http://192.168.0.15/dev/ storage/8320004456789/ emergency.do 8340004 456789 http://192.168.0.15/dev/ storage/8340004456789/ emergency.do 8360004 456789 http://192.168.0.15/dev/ storage/8360004456789/ emergency.do Chapter 4: Service processor Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Turning on automatic Windows updates or using the manual Windows update ■ method. Installing antivirus software that has been tested and approved by Hitachi. ■ SVP front panel The front panel of the physical SVP with Windows 10 Enterprise operating system is equipped with LEDs, a reset button, and a power button.
Page 46
Note: After the Initial Startup Wizard is complete, the SVP can be used in non- bridge mode. In this mode, the cables can be removed from SVP ports LAN3 and LAN4 and attached to switches. For more information, contact customer support. Chapter 4: Service processor Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
To avoid this situation, charge the battery for more than three hours at least once every six months. Chapter 5: Maintaining the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Observe the following instructions when removing cables form the storage system. To remove a SAS cable, pull the tab of the SAS cable (1) to release the latch and remove the SAS cable (2). Chapter 5: Maintaining the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 49
SAS cable (2). To remove a LAN cable, push the top of the LAN cable connector (1) to release the latch and remove the LAN cable (2). Chapter 5: Maintaining the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Appendix A: Storage system parts list The following parts list describes the standard and optional hardware components for the storage systems. For more information about the storage system, contact an Hitachi Vantara sales representative. VSP G700 parts list The VSP G700 includes the following standard and optional components.
Page 51
SFP for 32 Gbps Longwave 0-64 DW-F800-BAT Battery Note: 1. A DIMM of a particular capacity cannot be mixed with different capacities in a storage system configuration. Appendix A: Storage system parts list Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
(Windows 10 Enterprise) Drive tray and drive configuration The following table lists the supported maximum mountable drive trays and data drives for the VSP G700 storage system. Appendix A: Storage system parts list Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
10.0 m, 2-pole power cable with grounding terminal (AC 250 V, 13 A or 15 A-F6516-P620 Power cable for PDU (1) A-F6516-P630 Power cable for PDU (1) Appendix A: Storage system parts list Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 56
5 m SAS cable, including omega clips (2) DW-F800-SCQ10A 10 m SAS optical cable DW-F800-SCQ30A 30 m SAS optical cable DW-F800-SCQ1HA 100 m SAS optical cable Appendix A: Storage system parts list Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 57
30 m LC-LC optical cable for optical A-6515-JM50L 50 m LC-LC optical cable for optical A-6515-JM100L 100 m LC-LC optical cable for optical A-6515-JM200L 200 m LC-LC optical cable for optical Appendix A: Storage system parts list Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 58
Data and power cable model list Model number Specification A-6515-JM300L 300 m LC-LC optical cable for optical Appendix A: Storage system parts list Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
2. Can be mounted on the RKU rack. For the mounting, special rails for the rack and decoration panels are required separately depending on the number of the mounted storage systems. 3. The value is at maximum level. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 60
DB60 184 W Power 126 VA consumption (VA) 144 VA 130 VA DB60 191 VA Air flow (m /min) 2.2 (m /min) 2.2 (m /min) 1.6 (m /min) Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 61
2. Can be mounted on the RKU rack. For the mounting, special rails for the rack and decoration panels are required separately depending on the number of the mounted storage systems. 3. The value is at maximum level. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 62
1. When mounting storage system and mixing DBS, DBL, DBF and DB60 drive trays, the maximum mountable quantity (unit) may vary. 2. Available as spare or data disks. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 63
Up to 75.2º F (24º C) 5 years Up to 86º F (30º C) 5 years Up to 93.2º (34º C) 4 years Up to 104º (40º C) 3 years Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 64
Flash memory: 32 MB L3 cache memory: 4 MB SDRAM: 1 GB Data assurance method Data bus: Parity Cache memory: ECC (1 bit correction, 2 bit detection) Drive: Data assurance code Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
. The actual required power might exceed the value shown in the table when the tolerance is included. Environmental specifications The environmental specifications for the storage systems are described in the following table. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 67
14°F to 95°F (-10°C to 35°C) (-10°C to 50°C) Transport, -22°F to 140°F -22°F to 122°F (-30°C to 50°C) storage (-30°C to 60°C) Temperature 10°C or less change rate (°C/h) Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 68
CBL controller and drive trays Operating 20 or less (m/s (10 ms, half sine wave) Non-operating 50 or less (m/s (10 ms, half sine wave) Transport (packed) 80 or less Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 69
40ºC at an altitude of 950m (3000 feet) to 28ºC at an altitude of 3050m (1000 feet). The allowable ambient temperature is decreased by 1ºC for every 175m increase in altitude above 950m. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 70
Operating Gaseous contamination should be within ANSI/ISA S71.04-2013 G1 classification levels. Non-operating Recommends the data centers maintain a clean operating environment by monitoring and controlling gaseous contamination. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 71
Therefore, the rate of the noise occupied by high-frequency content is high. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 72
7.2 B to 8.1 B, according to the ambient temperature, drive configuration, and operating status. 4. When accessing the dense intermix drive tray, do not work for long times at the rear of the rack. Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 73
The acoustic noise level of 90 dB or less in the operating environment table represents the current operating environment guidelines in which Hitachi storage systems are designed and manufactured for reliable operation when placed 2 meters from the source of the noise.
Page 74
Environmental specifications State Condition Hitachi does not test storage systems and data drives (includes HDDs, SSDs, and FMDs) for compatibility with fire suppression systems and pneumatic sirens. Hitachi also does not provide recommendations or claim compatibility with any fire suppression systems and pneumatic sirens.
9.8m/s (1.0G) equivalent to NEBS (Network Equipment-Building System) Level3). Shared memory Using Hitachi software products, the number of pairs, migration plans, and pool capacities and virtual volumes depend on the amount of capacity of shared memory installed on the controller.
Page 76
Table 21 Minimum cache memory capacity required for shared memory function Shared Memory Function VSP G700 Base 128 GiB Extension1 128 GiB Extension2 256 GiB Extension3 256 GiB Appendix B: System specifications Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Establish connections from the controllers to the host computers. ■ Connect the storage system to the network, enabling storage system management ■ through Hitachi Command Suite or Hitachi Storage Advisor. Allow communication to the storage system from the SVP. ■ TCP/IP port assignments When you install your storage system, default ports must be opened to allow for incoming and outgoing requests.
Page 78
TCP/IP port assignments Port number Usage description Used by the SVP, Hitachi Storage Advisor, and Device Manager - Storage Navigatorto communicate through the HTTP protocol. UDP (SNMP uses this port to send traps from the storage system) . Used by SMI-S.
Page 79
S is not used. or later Automatic 88-02-0x -xx/00 allocation or later CommonJettySt HTTP 8080 88-02-0x -xx/00 or later CommonJettySt HTTP 8210 RestAPIServerS HTTP 9210 DeviceJettyStart HTTP 8081 Appendix C: Network access Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
■ Physical service processor connections The SVP is available as an optional, physical device provided by Hitachi Vantara or as a virtual guest host running on customer-provided ESX servers and VM/OS licenses and media. The SVP provides error detection and reporting and supports diagnostic and maintenance activities involving the storage system.
Page 81
SVP Guest OS (1 DKC) Windows 10 IoT Enterprise ■ 2 x vCPU ■ 1 virtual network adapter ■ 4 GB RAM ■ 120 GB disk space ■ Appendix C: Network access Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Serial-attached SCSI (SAS) cables are used to connect drive trays to controllers and other drive trays. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 83
Fibre Channel cable length based on cable size and port speed. Cable size Speed Maximum cable length 9 micron 1 Gbps 1 km (3281 ft) 2 Gbps 2 km Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Note: Due to high-speed serial data transfer via Fibre Channel, use high- quality FC cables that comply with the Fibre Channel-PH standard. The following figure shows FC direct connection and FC connection through a switch. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 85
114.8 ft (35 m) 328.08 ft (100 410.1 ft (125 m) — 32 Gbps 65.62 ft (20 m) 229.7 ft (70 m) 328.08 ft (100 — Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 86
Wavelength: (OMx) 850 nm LC-LC cable DXLC-2PS- 9/125 μm (longwave) SPC-xxM- Singlemode Wavelength: 10/125-2SR 1300 nm The following figure shows the connector used for optical interfaces. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Interface name Cable One side Other side LC-LC cable Optical Equivalent 50, 125 mm to DXLC-2P- Multimode connector connector PC-xxM- Wavelength: GC50, 850 nm 125-2SR (OMx) Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 88
LC connector type ■ Connector type: LC duplex receptacle connector ■ Interval: 6.25 mm flat type, two rows ■ Cable specifications for 10 Gbps iSCSI copper interface Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 89
50 m 10 Gbps 10GBASE-T STP ( use an RJ-45 LAN cable STP cable that suppresses radio noise) The following figure shows a 10 Gbps iSCSI cable. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
255 (maximum per iSCSI With Linux software port) initiator, the maximum number decreases. Path failover HDLM Supports Microsoft MPIO (Multi Path I/O) Link 10 Gbps SFP+ Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 91
When an iSCSI Port IPv6 is set to Enabled, verify the IPv6 router is connected to the same network, and then set IPv6 global address automatically. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 92
Header digest Supported Detects header error or data error with iSCSI communication. The storage system follows the host's digest setting. If digest is enabled, the performance degrades. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
ASCII-coded, hexadecimal, EUI-64 identifier. Example: eui.0123456789abcdef Managing cables Organize cables to protect the integrity of your connections and allow proper airflow around your storage system. Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 94
Fibre Channel 40 mm (1.73 inch) iSCSI optical 40 mm (1.73 inch) Category 5 Ethernet Four times the outside diameter of the cable 40 mm (1.73 inch) Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 95
Cabling full-width modules When cabling full-width modules, route the cables horizontally, so that they do not interfere when replacing a module. Ensuring adequate airflow Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
■ AC power cables Utility AC power standards for connector types and voltage levels vary by country. Hitachi provides a variety of power cables that facilitate using storage systems around the world. Hitachi power cables meet the safety standards for the country for which they are intended.
Page 97
South Africa 200-240 10, 16 SABS-164 Switzerland 200-240 SEV 1011 International 200-240 IEC 309 United 200-240 BS-1363 Kingdom International 200-240 IEC 309 International 200-240 IEC 309 Appendix D: Data and power cables Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Power cable usage guidelines Power cable usage guidelines Hitachi storage systems are intended for rack installation and ship with power cords. Installation and service requirements may require additional cords and cables to be ordered. The type of power cable required by a given installation is determined primarily by the: Type of AC line feed provided by the facility.
Appendix E: Power distribution units for Hitachi Universal V2 Rack The Hitachi Universal V2 Rack is equipped with specific power distribution units (PDU) for Americas, APAC, and EMEA regions. The PDUs can provide electrical power to the storage system in a single-phase or three-phase configuration.
Americas single-phase PDU 1P30A-15C13-3C19UL.P Americas single-phase PDU 1P30A-15C13-3C19UL.P The following figure and table describes the specifications of the PDU. Figure 2 Americas PDU for the Hitachi Universal V2 Rack (Single-phase PDU 1P30A-15C13-3C19UL.P) Part Number Region Phase Description 1P30A-15C13-3C19 Americas Single 208V, 30A (24A ■...
APAC and EMEA single-phase PDU 1P32A-18C13-3C19CE.P Figure 6 APAC and EMEA PDU for the Hitachi Universal V2 Rack (Single-phase 1P32A-9C13-3C19CE.P) Part Number Region Phase Description 1P32A-9C13-3C19C APAC and EMEA Single 230V max. 32A ■ 50Hz / 60Hz 9 IEC C13 + 3 IEC ■...
APAC and EMEA three-phase PDU 3P16A-9C13-3C19CE.P Figure 7 APAC and EMEA PDU for the Hitachi Universal V2 Rack (Single-phase 1P32A-18C13-3C19CE.P) Part Number Region Phase Description 1P32A-18C13-3C19 APAC and EMEA Single 230V max. 32A ■ CE.P 50Hz / 60Hz 18 IEC C13 + 3 ■...
APAC and EMEA three-phase PDU 3P16A-15C13-3C19CE.P Figure 8 APAC and EMEA PDU for the Hitachi Universal V2 Rack (Three-phase 3P16A-9C13-3C19CE.P) Part Number Region Phase Description 3P16A-9C13-3C19C APAC and EMEA Three 400V max. 3x ■ 16A 50Hz / 60Hz 9 IEC C13 + 3 IEC ■...
APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P Figure 9 APAC and EMEA PDU for the Hitachi Universal V2 Rack (Three-phase 3P16A-15C13-3C19CE.P) Part Number Region Phase Description 3P16A-15C13-3C19 APAC and EMEA Three 400V max. 3x ■ CE.P 16A 50Hz / 60Hz 15 IEC C13 + 3 ■...
Page 110
APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P Figure 10 APAC and EMEA PDU for the Hitachi Universal V2 Rack (Three-phase 3P32A-24C13-6C19CE.P) Part Number Region Phase Description 3P32A-24C13-6C19 APAC and EMEA Three 400V max. 3x ■ CE.P 32A 50Hz / 60Hz 24 IEC C13 + 6 ■...
PDUs and cable loops. Hitachi Universal V2 Rack rail kits Use rail kits to mount the Hitachi Virtual Storage Platform family storage system in a Hitachi Universal V2 Rack. The following tables list the rail kit information for the specified storage systems.
2. CGR: Corner guide rail kit A3BF-HK-GL-740-1. Hitachi Universal V2 Rack accessories The following table provides rack accessory information for VSP G series storage systems. Table 23 Accessories for the Hitachi Universal V2 Rack Storage system Front door Rear door...
Use caution when handling equipment with movable parts. Use caution when handling equipment with hot surfaces. Use caution when handling equipment prone to tipping over. Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Small form factor drive tray Small form factor drive tray Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Large form factor drive tray Large form factor drive tray Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
CMA (used to secure dense intermix drive tray) CMA (used to secure dense intermix drive tray) Battery Appendix G: Warning labels on the storage system Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 121
They will dispose of it for you. This nickel-metal hydride battery, which is designated as recycling product by a recycling promotion low, must be recycled. The mark posted on the Cache Backup Battery is a three-arrow mark that indicates a recyclable part. Appendix H: Environmental notices Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 122
Appendix I: Regulatory compliance This equipment has been tested and certified for compliance with the following standards. Appendix I: Regulatory compliance Hitachi Virtual Storage Platform G700 Hardware Reference Guide...
Page 123
All CB countries 1+A2 IEC60950-1:2005+A S_Mark Argentina 1+A2 TP TC 004/2011 Russia CNS 14336-1 BSMI Taiwan EN60950-1:2006+A1 CE marking 1+A1+A12+A2 Radio interference VCCI V-3/2015.4 VCCI Japan voluntary control Appendix I: Regulatory compliance Hitachi Virtual Storage Platform G700 Hardware Reference Guide...