Door Open Alarm Time Setting - IDTECK Star LX505 User Manual

Proximity / pin access controller
Hide thumbs Also See for Star LX505:
Table of Contents

Advertisement

This feature allows you to use the LX505 as a reader (rather than as a controller). If this
setting is set to USE, the LX505 sends 26bit Wiegand Output through two TTL output ports.
NOT USE: Normal TTL outputs will be activated.
USE: 26bit Wiegand outputs will be generated through TTL1 and TTL2 ports. When a
registered card is read, the "CARD SCCANNING OK" message will appear on
the LCD. (TTL1 : Data 0 TTL2 : Data 1)

12.2.8 Door Open Alarm Time Setting

The 'Door Open Alarm Delay' is the time period between the Door Open Time and the point
at which the Door Open Alarm starts ringing.
00: The alarm will ring if the door isn't closed after the Door Relay time.
01~98: The alarm will ring if the door is not closed after the door open time and over
the alarm delay time. (01~98 sec.)
99: No alarm.
Note | A Door Contact Sensor must be installed on the door for this application.