Mounting the 7810iR
The 7810iR must be mounted indoors. To mount the 7810iR, complete the following steps:
1. Detach the case back by pushing up into the two tabs located at the bottom of the 7810iR
with the blade of a screwdriver while pulling the case back and case front apart.
2. Locate the case back over the mounting surface such that the opening in the case back is
aligned with the wire/cable access opening (in the mounting surface) while passing the
wires/cable through the opening in the case back.
3. Secure the case back to the mounting surface using four screws (supplied).
Power Requirements
The 7810iR requires a 12.5 V DC, 300mA line input.
U L
For UL installations, the DC power supply must be powered by a Listed uninterruptible power
supply (UPS) with audible and visual indications of switchover to secondary power.
Manual Mode

General Information

As the name implies, Manual Mode is a standalone method of receiving Contact ID or
ADEMCO high-speed messages from a protected premise. Incoming messages are displayed
in the New Alarm Window of the 7810iR. An operator is required to silence an incoming
alarm and manually move it from the New Alarm window to the Alarm History window
using the appropriate touch keys on the GUI.
U L
Manual Mode and Fail to Manual Mode cannot be used with UL installations.
A programmable feature allows Manual Mode to be the 7810iR failure mode. When selected
during programming, Fail to Manual allows the 7810iR to automatically revert to Manual
Mode if the automation equipment or LRR line card fails. Refer to Section 6 for a detailed
description of the Fail to Manual feature.

Wiring the 7810iR For Manual Mode

1. Connect the 12V AUX terminal (pin 1) of the 7810iR to the DC (+) terminal of power
supply 7720V2TR.
2. Connect a jumper between 12V AUX terminal (pin 1) and 12V IN (pin 2, RED).
7810iR Setup