7810iR Internet Communication Module Installation and Setup Guide
Message
cccc nng4 rrrr 0
Key Indicator: "A" in 3rd channel
cccc ngA0 s0fm 0
Key Indicator: "D" in 3rd channel
cccc 00D0 010C 0
cccc 00D0 010E 0
cccc 00D0 020E 0
cccc 00D0 020C 0
cccc 00D0 0104 0
cccc 00D0 0103 0
cccc 00D0 0106 0
6-6
Definition
Subscriber Command Failure (Dialer reporting)
nn = number of the node reporting (01 to 15)
g = node group number (0 or 1)
4 = subscriber trouble message
rrrr = reason code:
0001 = Low signal strength
0002 = Frequency error
0003 = Modulation error
0004 = Keyed-on subscriber
0005 = Repeating alarm suppressed
0006 = Redundant supervision warning
0007 = Multiple nodes down
0010= Redundant supervision restore
0011 = Multiple nodes down restore
0012 = 2-Way radio internal tamper
0013 = Authentication – no response
0014 = Authentication violation
0015 = Authentication Initialized
* Messages for account # "0000" refer to the central
station.
A-type diagnostic (RF)
n = number of the node reporting (1-9, A-F)
g = node group number (0 or 1)
A = A-type diagnostic
s = signal strength (0-9, or A)
f = frequency (always "0", not used)
m = modulation level (always "0", not used)
Authorized radio or subscriber substitution
Unauthorized substitution attempt
Service termination alarm
Code download
Reset command sent
Comm inquiry sent
Test command sent
Applies to
A
A
M,C&I
M,C&I
M,C&I
M
A&M
A&M
A&M