Status Channel = 5 (Subscriber Trouble / Special Report) - Honeywell AlarmNet 7810iR Installation And Setup Gude

Internet communication module
Hide thumbs

Advertisement

Status Channel = 5 (Subscriber Trouble / Special Report)

Message
Key Indicator: Account # = "0000" or "0001"
0000 5555 5515 5
0001 5555 5515 5
0000 5555 5535 5
0001 5555 5535 5
0000 5555 1555 5
0001 5555 1555 5
0000 5155 5555 5
0001 5155 5555 5
NOTE: For subscriber reporting, each channel that displays these message types
corresponds to a particular type of event. Because there are eight channels, it is possible for
multiple events to be reported in multiple channels in only one message.
(Example: The message "cccc 1555 5355 5" indicates a fault on zone 1 and a restore on zone
6.)
cccc zzzz zzzz 5
cccc 5555 5515 5
Definition
Master Host Alarm
The 685 generates this message internally. It indicates a
failure to connect to the network. This may be caused by:
Antenna failure
Radio receiver failure
Substantial interference
Network outage
Master Host Alarm Restore
Master Host Alarm Reminder
Notifies the central station that the redundant receiver has
lost connection to the 685.
Check 685 Printer
Tells the C/S to refer to their printer for messages that
might not be reported through the automation system.
Fire Zone Supervisory Fault
z = zone number corresponding to the channel position (1
– 8)
1 = new zone fault
3 = zone restore
5 = normal zone condition
6 = previously report zone fault
Loss of ECP Supervision
('Master Host' type message for an individual subscriber)
Applies to 7845C when used in 4229 or 4204 modes only.
Section 6: Message Formats
Applies to
A, I & M
A, I & M
M & I
A & M
7720ULF or
7920SE only
7845C and
7845CZ
6-9