M-Bus Telegrams; Total Energy Counters 0,1,2,3; Active Tariff Number; Set Baud Rate Via Primary / Secondary Address (Snd_Ud) - Iskra MC320 User Manual

Measuring centres mc3x0x series energy meter; multimeter; network recorder
Table of Contents

Advertisement

APPENDIX D: M‐BUS 
 
Set Baud Rate via Primary / Secondary Address (SND_UD) 
This telegram enables to set the desired Baud Rate. The M‐BUS MC350 confirms the correct receipt by ACK. If 
the telegram was not received correctly the M‐BUS MC350 does not send an Acknowledgement. The (ACK) is 
sent by the M‐BUS MC350 in the Old Baud Rate. As soon as ACK is transmitted the M‐BUS Meter switches to the 
baud rate newly parameterized. If the MC350 now does not receive a new Telegram under the new baud rate 
within a period of 30 – 40 seconds, it automatically switches back to the old baud rate. This is apt to prevent that 
a faulty setting of the baud rate may interrupt communication. 
Set Primary Address via Primary / Secondary Address (SND_UD) 
This Telegram enables to set a new Primary Address. The M‐BUS MC350 confirms the correct receipt by ACK. If 
the telegram has not been correctly received the M‐BUS MC350 will not send an Acknowledgement. 
Set Secondary Address via Primary / Secondary Address (SND_UD) 
This Telegram enables to set a new Secondary Address. The M‐BUS MC350 confirms the correct receipt by ACK. 
If the telegram has not been correctly received the M‐BUS MC350 will not send an Acknowledgement. 
Secondary Address (UD) consists of: 
 Identification Number: 
 Manufacturer's Code: 
 Version Number: 
 Medium: 
Reset, Restart M‐BUS MC350 via Primary / Secondary Address (SND_UD) 
This Telegram resets / restarts M‐BUS MC350. The M‐BUS MC350 confirms correct receipt by ACK. If the telegram 
was not correctly received the M‐BUS MC350 will not send an acknowledgement. 
 
M‐Bus Telegrams 
Total Energy counters 0,1,2,3 
Energy counters could represent: +/‐ active energy, +/‐reactive energy or apparent energy and one of 4‐th tariff. 
 
 
DIF 
DIFE 
 
 
T0: 
04 
none 
T1: 
84 
10
T2: 
84 
20
T3: 
84 
30
T4: 
84 
80
A+: 
 
A‐: 
 
R+: 
 
R‐: 
 
App: 
 
n ‐ 0...7 
 
Active Tariff number 
Tariff number in progress (1 to 4)
 
DIF 
DIFE 
 
01 
DATA: value represent as 8‐bit integer 
Measuring centres – MC320, MC330, MC350 & MC350H ‐ User's Manual
 
00000000 – 99999999 
73 26 
01 – FF 
02 
DIFE 
VIF
VIFE
 
none 
none 
none 
none 
10 
 
0n
none
 
8n
3C
 
FB 
82
 
FB
82
 
FB
84
 
DIFE 
VIF
VIFE
 
FF
01
8‐digit Secondary Address number 
2 Byte Company Constant (
1 Byte 
1 Byte Constant Electricity 
VIFE
VIFE
none
none
none
none
7n
none
Fn
3C
7n
none
VIFE
VIFE
Iskra = "73 26
") 
DATA 
xx.xx.xx.xx 
n‐3 
*10 
Wh 
n‐3 
*10 
Wh 
n‐3 
*10 
varh 
n‐3 
*10 
varh 
n‐3 
*10 
VAh 
DATA 
xx
69