Wrong connection warning   
If all phase currents (active powers) do not have same sign (some are positive and some negative) and/or if phase 
voltages and phase currents are mixed, the warning will be activated if this setting is set to YES. This warning is 
seen only on remote display. 
Energy flow direction   
This setting allows manual change of energy flow direction (IMPORT to EXPORT or vice versa) in readings tab. It 
has no influence on readings sent to communication or to memory. 
CT connection   
If this setting is set to REVERSED it has the same influence as if CT's would be reversely connected. All power 
readings will also change its sign. 
Communication 
Serial Communication     
They define parameters that are important for the operation in RS485 network or connections with PC via RS232 
communication. Factory settings of communication are #33\115200,n,8,2 (address 1 to 247\rate 2400 to 115200 
b/s, parity, data bits, stop bit). 
 
 Main menu  Settings  Communication  
USB Communication   
Has no setting. Device is automatically recognized in Windows environment if device driver has been correctly 
installed.  For  more  detailed  information  how  to  handle  device  with  USB  communication  use  Help  section  in 
MiQen software. 
Service USB Communication (MC330 and MC320 only)   
Has no setting. Device is automatically recognized in Windows environment if device driver has been correctly 
installed.  For  more  detailed  information  how  to  handle  device  with  USB  communication  use  Help  section  in 
MiQen software 
 
 PLEASE NOTE 
Service USB is intended only for parameterisation of the meter and is not galvanic separated. 
Advantage  is  that  in  this  case  meter  does  not  need  a  power  supply  to  communicate. 
Communication via service port is time limited. 
 
 
 WARNING! 
Service USB communication is not galvanic separated! 
 
When using service USB communication, power supply and measuring voltages need to be 
disconnected! 
 
PROFIBUS Communication   
To set Profibus communication please see Appendix C. 
M‐Bus Communication   
To set M‐Bus communication please see Appendix D. 
28 
 
Measuring centres – MC320, MC330, MC350 & MC350H ‐ User's Manual
SETTINGS 
 