Counter divider (Individual counter Resolution – MiQen 2.x and above)
The counter divider additionally defines precision of a certain counter, according to settings of common energy
exponent.
An example for 1kW of consumed active energy in the first tariff:
Common energy exponent
Counter divider
Example of result, displayed
Tariff clock
Basic characteristics of a program tariff clock:
4 tariffs (T1 to T4)
Up to 4 time spots in each Day program for tariff switching
Whichever combination of valid days in a week or holidays for each program
Combining of day groups (use of over 4 time spots for certain days in a week)
Separate settings for 4 seasons a year
Up to 20 settable dates for holidays
OPERATION OF INTERNAL TARIFF CLOCK
Tariff status is displayed in the Info menu.
Example of display for selected Active tariff:
Main menu Info OK
Day program sets up to 4 time spots (rules) for each day group in a season for tariff switching.
A date of real time clock defines an active period. An individual period is active from the period starting date to
the first next date of the beginning of other periods.
The order of seasons and starting dates is not important, except when two dates are equal. In that case the
season with a higher successive number has priority, while the season with a lower number will never be active.
If no starting date of a season is active, the active period is 1.
If the present date is before the first starting date of any period, the period is active with the last starting date.
Example of settings:
Season
Season start day
Season 1:
15.02
Season 2:
30.10
Season 3:
‐
Season 4:
01.06
Date
Active season
01.01. ‐ 14.02.
2 (last in the year)
15.02. ‐ 31.05.
1
01.06. ‐ 29.10.
4
30.10. ‐ 31.12.
2
32
0
1
2.577 kWh 0.2577 MWh
or
Measuring centres – MC320, MC330, MC350 & MC350H ‐ User's Manual
2
2
1
100
25.77 MWh
or
SETTINGS