APPENDIX A: MODBUS PROTOCOL 
 
100% values calculations for normalized measurements 
Un = 
(R40147 / R40146) * R30015 * R40149
In = 
(R40145 / R40144) * R30017 * R40148
Pn = 
Un*In 
It = 
In 
Connection Mode: 1b 
It = 
3*In 
Connection Modes: 3b, 4b, 3u, 4u
Pt = 
Pn 
Connection Mode: 1b 
Pt = 
3*Pn 
Connection Modes: 3b, 4b, 3u, 4u
Fn = 
R40150 
 
Register 
Content 
30015 
Calibration voltage 
30017 
Calibration current 
 
Register table for the basic settings 
Register  Content 
40143 
Connection Mode 
 
 
 
 
 
 
 
 
 
 
40144 
CT Secondary 
40145 
CT Primary 
40146 
VT Secondary 
40147 
VT Primary 
40148 
Current input range (%) 
40149 
Voltage input range (%) 
40150 
Frequency nominal value  T1 
 
 
Measuring centres – MC320, MC330, MC350 & MC350H ‐ User's Manual
 
Type  Ind
Values / Dependencies
T1 
0
No mode
 
1
1b ‐ Single Phase
 
2
3b ‐ 3 phase 3 wire balanced
 
3
4b ‐ 3 phase 4 wire balanced
 
4 3u ‐ 3 phase 3 wire unbalanced
 
5 4u ‐ 3 phase 4 wire unbalanced