Planning/Configuring

6.2 Configuring the DM-F LOCAL

6.2
Configuring the DM-F LOCAL
Note
The safety-related functions can only be configured using the DIP switches.
Table 6- 1
Factory setting
OFF
Without cross-circuit detection
1 NC + 1 NO evaluation
2 x 1-channel
Debouncing time for sensor inputs ∼ 50 ms
Sensor input automatic start
Cascading input automatic start
With start-up testing
Automatic starting after power failure (not
permissible in conjunction with start-up testing)
No function
No function
Automatic starting after power failure. Risk of death or serious injury.
In the case of automatic starting after a power failure, the enabling circuits are connected
without pressing the Start button.
The desired configuration of the DM-F Local can be stored in SIMOCODE pro using the
SIMOCODE ES software (e.g. for documentation purposes). The stored configuration is then
compared with the actually effective settings on the DM-F Local (i.e., the settings defined
with the DIP switches). If the stored configuration is not the same as the effective
configuration, the following status message appears: "DM-FL Configuration deviates".
40
Schematic
DANGER
DIP switch
ON
No.
1
With cross-circuit detection
2
2 NC evaluation
3
1 x 2-channel
4
Debouncing time for sensor inputs ∼ 10 ms
5
Sensor input monitored start
6
Cascading input monitored start
7
Without start-up testing
8
No automatic starting after power failure
-
No function
-
No function
SIMOCODE pro - Fail-Safe Digital Modules