Flowserve Logix 3400MD User Instructions page 28

Digital
Hide thumbs Also See for Logix 3400MD:
Table of Contents

Advertisement

Fieldbus
Fieldbus Variable
Block
Name
Index
54
HOURS_SINCE_RESET
55
HOURS_LIFETIME
86
ERROR_HIST
Signature Parameters
56
SIG_START
57
SIG_STOP
58
SIG_RATE
59
SIG_HOLD
61
SIG_FLAGS
60
SIG_INDEX
88-113
SIG_DATAn
System Setup & Special Diagnostics Parameters
33
USER_INTERFACE_
INSTANT
34
USER_INTERFACE_
ACTIVE
24
TEST_MODE
62
TRAVEL_ACCUM_UNITS
63
PRESSURE_UNITS
64
INTERNAL_TEMP_UNITS
65
XD_FSTATE_OPT
66
ELECTRONICS_SN
67
SOFTWARE_VER_MAJOR
68
SOFTWARE_VER_MINOR
69
SOFTWARE_DATE_CODE
73
FB_POSITION_FILTER
75
LOAD_EE_DEFAULTS
System Setup & Special Diagnostc Fieldbus Only Parameters
28
Transducer
Fieldbus
Block
Datatypes
Register
XDTB_MAIN
FLOAT
138
XDTB_MAIN
FLOAT
139
XDTB_TECH
ARRAY
140
XDTB_MAIN
FLOAT
142
XDTB_MAIN
FLOAT
143
XDTB_MAIN
FLOAT
144
XDTB_MAIN
FLOAT
145
XDTB_MAIN
BIT_STRING
146
XDTB_MAIN
UNSIGNED 16
147
XDTB_TECH
ARRAY
148
XDTB_TECH
BIT_STRING
36
XDTB_TECH
BIT_STRING
37
XDTB_MAIN
BIT_STRING
32
XDTB_MAIN
UNSIGNED 8
150
XDTB_MAIN
UNSIGNED 8
151
XDTB_MAIN
UNSIGNED 8
152
XDTB_MAIN
UNSIGNED 8
153
XDTB_MAIN
VISIBLE_
155
STRING
XDTB_MAIN
UNSIGNED 16
156
XDTB_MAIN
UNSIGNED 16
157
XDTB_MAIN
VISIBLE_
158
STRING
XDTB_TECH
UNSIGNED 16
162
XDTB_TECH
UNSIGNED 8
173
Logix 3400MD Digital Positioner FCD LGENIM3404-00 – 9/09
Logix Positioner
Fix
Type
Pt
Variable Name
Rd
U_LONG
/10
Reset_Hours
U_LONG
/10
Lifetime_Hours
U_CHAR
NO
ErrorHist [16]
S_INT
/100 SIGstart
S_INT
/100 SIGstop
U_INT
/100 SIGtime
U_INT
/100 SIGhold
U_CHAR
NO
SIGflags
U_INT
NO
ReadSigIndex
S_INT [24]
/100 SigData
U_INT
NO
UI_Instant
U_INT
NO
UI_Saved
U_CHAR
NO
control_
disable_flg
U_CHAR
NO
TravelUnits
U_CHAR
NO
PressUnits
U_CHAR
NO
TempUnits
U_CHAR
NO
Fail_mode
U_CHAR
NO
ESN [8]
U_INT
NO
ESR_Major
U_INT
NO
ESR_Minor
STRING
NO
ESR_Build [6]
U_INT
NO
FB_Depth
U_CHAR
NO
EEmode
R/W
Description
R
Status, System, Time Elapsed,
Mem Reset
R
Status, System, Time Elapsed,
Lifetime
R
History of the last error/blink
codes
NRW
Config, Signature, Starting
Command in %
NRW
Config, Signature, Stopping
Command in %
NRW
Time that a Signature takes to
complete a ramp cycle
NRW
Time to continue to log
signature data after reaching
SIG_STOP
NRW
Signture status and command
flags
NRW
Index into the Signature Data
Array
R
Signature Data Array
R
Curent hardware DIP switch
and GAIN control seetings - not
applied to control algorythms.
RW
Setup button and DIP switch
setting currently applied to
control algorythms
RW
Turns on and off spceial
diagnostic capabilities
SRW
Setup, Units, Travel Distance
SRW
Setup, Units, Pressure
SRW
Setup, Units, Temperature
SRW
NR
Electronics Serial Number, used
for initial PD tag
NR
Software Revision Major
NR
Software Revision Minor
SRW
Embedded Software Revision
Date Stamp
SRW
Setup, Dampening, Position,
Depth
RW
Test, FRAM, Mode Setting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents