Flowserve Logix 3400MD User Instructions page 27

Digital
Hide thumbs Also See for Logix 3400MD:
Table of Contents

Advertisement

Fieldbus
Fieldbus Variable
Transducer
Block
Name
Index
32
PRESS_CTRL_
XDTB_MAIN
WINDOW
33
FINAL_VALUE_
XDTB_MAIN
CUTOFF_HI
34
FINAL_VALUE_
XDTB_MAIN
CUTOFF_LO
42
FINAL_VALUE_
XDTB_TECH
CUTOFF_
HYSTERESIS
35
STOP_HI_POS
XDTB_MAIN
36
STOP_LO_POS
XDTB_MAIN
37
STROKE_TIME_
XDTB_MAIN
OPEN_LIM
38
STROKE_TIME_
XDTB_MAIN
CLOSE_LIM
43
CURVE_X
XDTB_TECH
43
CURVE_X
XDTB_TECH
44
CURVE_Y
XDTB_TECH
44
CURVE_Y
XDTB_TECH
Control: Calibration Parameters
25
CALIBRATE
XDTB_MAIN
45
STROKE_TIME_CAL
XDTB_TECH
46
STROKE_TIME_
XDTB_TECH
DOWN
47
STROKE_TIME_UP
XDTB_TECH
48
HALL_DOWN
XDTB_TECH
49
HALL_UP
XDTB_TECH
50
HALL_RANGE
XDTB_TECH
51
HALL_AD_cOUNT
XDTB_TECH
52
HALL_NULL_PCT
XDTB_TECH
53
FB_ZERO
XDTB_TECH
Fieldbus
Block
Datatypes
Register
FLOAT
54
FLOAT
59
FLOAT
60
FLOAT
61
FLOAT
62
FLOAT
63
FLOAT_S
64
FLOAT_S
65
FLOAT
66
FLOAT
67
FLOAT
68
FLOAT
69
UNSIGNED 8
33
FLOAT
70
FLOAT
71
FLOAT
72
UNSIGNED 16
75
UNSIGNED 16
76
UNSIGNED 16
77
UNSIGNED 16
78
UNSIGNED 16
79
UNSIGNED 16
80
Logix 3400MD Digital Positioner FCD LGENIM3404-00 – 9/09
Logix Positioner
Fix
Type
Pt
Variable Name
Rd
S_INT
/100
PS_Window
S_INT
/100
MAXcutoff
S_INT
/100
MINcutoff
S_INT
/100
MPChyst
S_INT
/100
SoftStopHigh
S_INT
/100
SoftStopLow
U_INT
NO
StrokeOpenTime
U_INT
NO
StrokeCloseTime
S_INT
/100
CURVEx [1-11]
S_INT
/100
CURVEx [12-21]
S_INT
/100
CURVEy [1-11]
S_INT
/100
CURVEy [12-21]
U_CHAR
NO
Cal_State
U_INT
/100
StrokeTime
U_INT
/100
StrokeTimeDn
U_INT
/100
StrokeTimeUp
U_INT
NO
Hall_Down
U_INT
NO
Hall_Up
U_INT
NO
Hall_Range
AD_REG
NO
Hall_Instant
S_INT
NO
Hall_Null
U_INT
NO
FB_Zero
R/W
Description
SRW
Setup, Pressure Control, Window
Size
SRW
Setup, MPC, Tight Shutoff
Threshold, Open
SRW
Setup, MPC, Tight Shutoff
Threshold, Closed
SRW
Setup, MPC, Tight Shutoff Hysteresis
SRW
Setup, Soft Stop Limit, Upper
SRW
Setup, Soft Stop Limit, Lower
NRW
Setup, Stroke Delay Time, Opening
NRW
Setup, Stroke Delay Time, Closing
SRW
Setup, SW Characterization, X-Axis,
Points 1-11
SRW
Setup, SW Characterization, X-Axis,
Points 12-21
SRW
Setup, SW Characterization, Y-Axis,
Points 1-11
SRW
Setup, SW Characterization, Y-Axis,
Points 12-21
RW
Test, Calibration, Mode Setting
R
Calibration, Measured Stroke Time
R
Calibration, Measured Stroke Time
R
Calibration, Measured Stroke Time
SRW
Calibration, Hall Sensor, A/D Counts,
Down Position
SRW
Calibration, Hall Sensor, A/D Counts,
Up Position
SRW
Calibration, FB, Valve Stem, A/D
Counts, Range
R
Status, Hall Sensor, A/D Counts,
Instantaneous
SRW
Calibration, Hall Sensor, A/D Counts,
Null Position
SRW
Caliberation, FB, Valve Stem, A/D
Counts, @Zero%
flowserve.com
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents