Riello BeSMART Installer And User Manual page 70

Wifi box and boiler rf receiver
Hide thumbs Also See for BeSMART:
Table of Contents

Advertisement

Parameter
27 SEnS
ESC
MODE
28 FCLO
ESC
MODE
Description
Enabling/disabling room sensor to activate
pure climate control (thermoregulation from
a single external probe). Default set to
ON. This value can be set to ON or OFF.
In AUTO
, MAN
operating modes only, by setting this pa -
rameter to OFF the heating/cooling request
is processed as follows:
− In ON/OFF mode, the heating/cooling
request is always active (relay closed)
if the T3 (comfort) time period is active.
− In OTBus mode, the heating request
is always active (only with the exter -
nal probe connected to the boiler or
the external web probe via the APP)
and the heating setpoint temperature
is calculated using the external probe
value only. The value set for parameter
26 (tSFt) is subtracted from the heat -
ing delivery setpoint calculated by the
BeSMART (tSEt), only in AUTO
operating mode, during the T2 (econ -
omy) or T1 (anti-freeze) time period.
9
This function uses one BeSMART only.
Time display setting. Default set to 24-hour clock.
The format can be set to the 12- or 24-hour clock.
Setting the parameter to 12H, the field is display
in the 12-hour a.m./p.m. format.
70
and PARTY