Advertisement

5. Execute a complete compilation of the S7 program.
6. Download changes to the automation system.
Note
If you use SFCs in your project, please note that you need to update the SFC blocks.
Additional information
SFC Readme
7.4

Adaptation of OS-relevant settings

7.4.1

Overview of Adaptation of OS-relevant Settings

Overview of the procedure
Step
15
16
User interface and design
After the software update, the design of the user interface for process mode must be set to
the following:
WinCC 3D
This setting is available automatically in projects created as of PCS 7 V8.0.
Other designs are not approved for PCS 7.
Software update without utilization of new functions
Service Manual, 03/2016, A5E36200133-AA
NOTICE
Updating a redundant OS in runtime
Updating according to the manual
Control Systems ; Guidelines for updating a redundant OS in runtime
If you update a redundant OS during operation, do not load the AS until phase 3 (in step
Process Control System PCS 7; Fault-tolerant Process Control Systems manual).
6 of the
Action
Synchronize OS basic pictures, local computer actions,
and faceplates (Page 56)
Update picture objects (Page 59)
Adaptations in the PCS 7 project on the ES

7.4 Adaptation of OS-relevant settings

Process Control System PCS 7, Fault-tolerant Process
ES
OS serv‐
OS cli‐
er
ent
X
X
AS
55