12.Drag-and-drop the selected PROFIBUS CP to the controller slot in the station window.
The "Properties ..." dialog box opens.
13.Select the entry of the associated bus system from the "Subnet" list.
14.Click "OK".
The "Insert master system" dialog box opens.
15.Select the entry of the associated bus system from the "Subnet" list.
16.Click "OK".
17.Select the Station > Save and Compile menu command.
7.2.7

How to configure the SIMATIC PDM Server

This section only applies to plants with a maintenance station.
Requirements
● The project/multiproject has been created.
● The SIMATIC PDM (Server) software package is installed on the Engineering Station.
Note
Requirements for use of SIMATIC PDM
Observe the conditions for the use of SIMATIC PDM versions.
Information is available in the SIMATIC PDM Readme (online).
● Specifying the name of the PC station (computer name)
You can find information about this in the documentation
PCS 7 - PC Configuration .
Note
The following names must be identical when you configure an OS or BATCH server and
an engineering station:
● Computer name
● Name of the PC station
Procedure
1. Select the Options > SIMATIC PDM > Settings command in SIMATIC Manager.
The "SIMATIC PDM settings" dialog box opens.
2. Select the "Maintenance Station" tab.
Software update without utilization of new functions
Service Manual, 03/2016, A5E36200133-AA
Adaptations in the PCS 7 project on the ES
7.2 General adaptations
Process Control System PCS 7;
51