4. Perform the following sequence of tasks for all OSs in the multiproject that have stored data
on the CAS (OS servers and single-station systems):
– Open the "Backup Configuration" tab in the "Properties" dialog of the PC station.
– Clear the "Backup enabled" check box for the following options:
Note
CAS backup configuration
If there is no longer a CAS computer in the project but the destination paths are entered,
a process control error is generated at each segment transition.
5. Perform the following sequence of tasks for all operator stations in the multiproject that
have a CAS assignment:
– Select the OS project in the component view of the SIMATIC Manager on the PC station.
– Select the menu command Options > OS > Assign OS Server....
– In the list of OS servers, check the following:
– Clear the check box for the PC station of the CAS.
6. Create a new PC station for the Process Historian in the project.
7. Configure a new PC station for the Process Historian.
You can find additional information about this in the documentation
PCS 7; Engineering System .
Save and compile the configuration.
8. Set the properties in the SIMATIC Manager. For this purpose, select the Process Historian's
PC station and then select the shortcut menu command Object properties.
9. Enter the computer name in the "Computer name" group or activate the "Computer name
identical to PC station name" check box.
10.Click "OK".
The "Properties" dialog box closes.
7.6

Adaptations for the Maintenance Station

7.6.1

Overview of the Maintenance Station update

Perform additional steps for updating an MS server.
Software update without utilization of new functions
Service Manual, 03/2016, A5E36200133-AA
- Tag Logging > Archive configuration > Tag Logging Fast
- Tag Logging > Archive configuration > Tag Logging Slow
- Alarm Logging > Archive configuration > Message archive
The "Assign OS Server ..." dialog box opens.
Make sure that the check box for the OS server with the data you want to visualize on
this operating station is selected.
Adaptations in the PCS 7 project on the ES

7.6 Adaptations for the Maintenance Station

Process Control System