3. Select the current version of the OPC Server from the hardware catalog at SIMATIC PC
Station > User application > OPC Server and drag-and-drop it to the position of the OPC
Server.
4. Click "OK" to confirm the replacement of the OPC Server.
5. Save and compile your changes.
6. Select the "OPC Server" object in the rack.
7. Select the menu command Station > Properties.
8. Open the "SNMP" tab.
9. Click the "Export Tags for WinCC" button.
10.Select the Station > Save and Compile menu command.
11.Repeat steps 1 to 5 if using the MS Server in a redundant MS multiple station system.
12.Perform the following actions if the project contains field devices that were configured in
SIMATIC PDM:
– Select the Options > SIMATIC PDM > Settings command in SIMATIC Manager.
– Select the "Maintenance Station" tab.
– Enter the file path of the PCS 7 project.
– Click "OK".
Updating SIMATIC PDM
Install SIMATIC PDM from the
PDM Readme.
When you open a project in SIMATIC Manager, the SIMATIC PDM-related project data is
updated automatically.
Note
Updating SIMATIC PDM up to V8.0
During the update of projects with SIMATIC PDM up to V8.0, new PLT IDs are assigned to the
configured ASSETMON objects. Then, perform the following steps:
● Adapt these PLT IDs to the corresponding ASSETMON block instances.
● Compile the automation systems.
● Create the diagnostics screens again.
● Compile the corresponding operator stations.
Software update without utilization of new functions
Service Manual, 03/2016, A5E36200133-AA
The "SIMATIC PDM settings" dialog box opens.
Adaptations in the PCS 7 project on the ES
7.6 Adaptations for the Maintenance Station
Process Control System; SIMATIC PCS 7 DVD. Refer to the
65