Updating SIMATIC BATCH stations
Information on updating SIMATIC BATCH is available in the following documentation:
● Manual
SIMATIC BATCH Readme ; Part B, Installation
●
Note
Note the following when updating the software from PCS 7 V7.1 SP4 (with SIMATIC BATCH)
to PCS 7 V8.2 (with SIMATIC BATCH):
● No batches should be actively running, because the BATCH database is restored from a
backup for the software update.
● To save the project "with reorganization", you first need to manually replace the BATCH
application in the PC stations in HW Config.
● Set the BATCH Start Coordinator to "Manual" start mode before you update the software.
It is essential that you observe these points when you prepare the software update. You can
find additional information on this in the section "Overview of preparations (Page 30)".
Software update without utilization of new functions
Service Manual, 03/2016, A5E36200133-AA
Process Control System PCS 7; SIMATIC BATCH