7
|
Technical data

7.7.2 Overview of field settings for indoor units

The overview lists all possible settings for the indoor units. The availability of the setting depends on the indoor
unit type, see "Field settings as per type indoor unit". Bold content is default setting.
See indoor unit or remote controller manuals for more detailed information to access the field settings.
st
Setting
1
code
10/20
0
Filter contamination (time between 2 filter cleaning
display indications)
1
Long life filter type
2
Indoor thermostat sensor selection (no effect when
used in conjunction with presence sensor BRYQ)
3
Filter sign display
6
Air thermistor selection in group wiring P1/P2
7
Absence delay detecting time (presence sensor)
9
central control
11/21
1
Similtaneous operation setting
2
Fan OFF at thermostat OFF
3
Fan setting of heating
Service manual
112
nd
Description function
2
code
01
02
01
02
03
04
01
02
03
04
01
02
01
02
01
02
01
02
01
02
01
02
01
02
03
Description setting
Light
Heavy
Long life filter
Ultra long life filter
(option)
No maintenance filter
Oil guard filter
Use both the unit sensor (or remote sensor if installed)
AND the remote controller sensor.
Use return air sensor only (or remote sensor if
installed).
Use remote controller sensor only.
Use only remote control thermostat (priority on floor
temperature)
Display
Do not display
Return air thermistor (individual units)
Thermistor designated by field setting 20‑2
30 minutes
60 minutes
Accept
Ignore
Unified setting
Individual setting
Normal
OFF
Standard
Slight increase (* 1.05)
Increase ( * 1.10)
Note
ESIE22-01 – 2022.02
FAA71+100BUV1B