Mounting The Shield Plate And Emc Connecting Bracket - Siemens SINAMICS G120 Hardware Installation Manual

Power modules pm240p-2, ip20
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

4.4.3

Mounting the shield plate and EMC connecting bracket

Mounting the shield plate and EMC connecting bracket, FSD ... FSF
Use the shield plate provided for strain relief of the line and motor cable – as well as the shield
support for the motor cable.
If you are using the inverter without filter, then you do not require the EMC connecting bracket.
In this case, attach the shield plate to the inverter without the EMC connecting bracket
If you are using an inverter with integrated line filter, then mount the shield plate and EMC
connecting bracket as described below.
Note
Brake relay
If you are using a brake relay to control a motor brake, then mount the brake relay at the rear
of the lower shield plate before you attach the shield module to the inverter.
Procedure - FSD and FSE
Proceed as follows to mount the EMC connecting bracket and the shield plate:
1. Attach the EMC connecting bracket to the shield plate
2. Then slide the shield module into the inverter, so that it is held in the inverter
clamping spring. The shield module is located correctly if it can be easily withdrawn out of
the inverter without any resistance.
3. After you have ensured that it is correctly located, fix the shield module using the four screws
You have correctly mounted the EMC connecting bracket and the shield plate.
PM240P-2 Power Modules
Hardware Installation Manual, 11/2016, A5E37800827C AB
Motor holding brake (Page 85)
.
Installing/mounting
4.4 Mounting the Power Modules
.
by the
33