Vega VEGABAR 52 Operating Instructions Manual page 40

4...20 ma/hart
Hide thumbs Also See for VEGABAR 52:
Table of Contents

Advertisement

6 Set up with the indicating and adjustment module PLICSCOM
Reset
Menu section
Basic settings
Display
Service
Menu section
Basic settings
Display
Service
40
Application
l
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" (sensor-specific basic adjustment) is carried out, the
sensor resets the values of the following menu items to the reset
values (see chart):
Function
Zero/Min. adjustment
Span/Max. adjustment
Density
Density unit
Damping
Linearisation
Sensor-TAG
Displayed value 1
Displayed value 2
Display unit
Scaling
Decimal point indication
Current output - characteristics
Current output - failure
Current output - min. current
Current output - max. current
The values of the following menu items are not reset with "Reset:
Function
Unit of measurement
Temperature unit
Position correction
Lighting
SIL
Language
HART mode
7)
Application
With instruments with signal output 4 ... 20 mA/HART
7)
Reset value
Measuring range begin
Measuring range end
1 kg/l
kg/l
1 s
Linear
Sensor
bar
%
Volume/l
0.00 to 100.0
8888.8
4 ... 20 mA
< 3.6 mA
3.8 mA
20.5 mA
Reset value
No reset
No reset
No reset
No reset
No reset
No reset
No reset
No reset
VEGABAR 52 • 4 ... 20 mA/HART

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents