6 Set up with the indicating and adjustment module PLICSCOM
Carry out a position cor-
rection
Carry out min. adjust-
ment
34
Unit of measurement
Density
0001000
kg/dm³
Enter the requested density value with [->] and [+], confirm with
6
[OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
à Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
Activate in the menu item "Position correction" the selection with
1
[OK].
Position correction
Offset
=
P
+0000 mbar
53 mbar
Select with [->], e.g. to accept actual measured value.
2
Position correction
Accept current measured
value?
Accept
Edit
Confirm with [OK] and move to min.(zero) adjustment with [->].
3
Proceed as follows:
Edit the % value in the menu item "Min. adjustment" with [OK].
1
Min. adjustment
+000.0 %
=
+0000.0 mbar
0000.0 mbar
Set the requested percentage value with [+] and [->].
2
Confirm with [OK] and edit the requested mbar value.
3
Set the requested mbar value with [+] and [->].
4
Selection options: °C, °F.
3)
3)
VEGABAR 52 • 4 ... 20 mA/HART