CHAPTER 4: MODBUS MEMORY MAP
Table 3: Modbus Memory Map (Sheet 30 of 40)
ADDR
1844
Current Demand Relays
1845
Current Demand Pickup
REAL POWER DEMAND (read/write setpoints)
1848
Real Power Demand Function
1849
Real Power Demand Measurement Type
184A
Real Power Demand Thermal 90% Response
184B
Real Power Demand Time Interval
184C
Real Power Demand Relays
2
Real Power Demand Pickup
184D
REACTIVE POWER DEMAND (read/write setpoints)
1850
Reactive Power Demand Function
1851
Reactive Power Demand Measurement Type
1852
Reactive Power Demand Thermal 90% Response
1853
Reactive Power Demand Time Interval
1854
Reactive Power Demand Relays
2
Reactive Power Demand Pickup
1855
APPARENT POWER DEMAND (read/write setpoints)
1858
Apparent Power Demand Function
1859
Apparent Power Demand Measurement Type
185A
App. Power Demand Thermal 90% Response
185B
Apparent Power Demand Time Interval
185C
Apparent Power Demand Relays
2
Apparent Power Demand Pickup
185D
PULSE OUTPUTS (read/write setpoints)
1860
Pulse Output Function
1861
Positive Watthours Pulse Output Relays
1862
Positive Watthours Pulse Interval
1863
Negative Watthours Pulse Output Relays
1864
Negative Watthours Pulse Interval
1865
Positive Varhours Pulse Output Relays
1866
Positive Varhours Pulse Interval
1867
Negative Varhours Pulse Output Relays
1868
Negative Varhours Pulse Interval
ANALOG INPUT SETUP (read/write setpoints)
1880
Analog Input Name (10 words)
188A
Analog Input Units (3 words)
188D
Analog Input Range
188E
Analog Input Minimum Value
188F
Analog Input Maximum Value
ANALOG INPUT THRESHOLD 1 (read/write setpoints)
9
Analog Threshold 1 Function
18A0
18A1
Analog Threshold 1 Relays
18A2
Analog Threshold 1 Pickup
18A3
Analog Threshold 1 Delay
1
Analog Threshold 1 Pickup Type
18A4
18A5
Analog Threshold 1 Dropout Ratio
ANALOG INPUT THRESHOLD 2 (read/write setpoints)
18A8
Analog Threshold 2 Function
18A9
Analog Threshold 2 Relays
18AA
Analog Threshold 2 Pickup
18AB
Analog Threshold 2 Delay
1 2 3 4 5 6 7 8 9 10 11 12 13
For explanation of Table footnotes, see the Memory Map Notes at the end of this table.
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DESCRIPTION
5
RANGE
UNITS
---
---
10 to 10000
A
---
---
---
---
---
---
---
---
---
---
0.1 to 3000.0
MW
---
---
---
---
---
---
---
---
---
---
0.1 to 3000.0
Mvar
---
---
---
---
---
---
---
---
---
---
0.1 to 3000.0
MVA
---
---
---
---
0 to 6553.5
MWh
---
---
0 to 6553.5
MWh
---
---
0 to 6553.5
Mvarh
---
---
0 to 6553.5
Mvarh
---
---
---
---
---
---
0 to 65535
Units
0 to 65535
Units
---
---
---
---
0 to 65535
Units
0 to 60000
s
---
---
2 to 20
%
---
---
---
---
0 to 65535
Units
0 to 60000
s
MEMORY MAP
TYPE
DEFAULT
F57
None
F1
1000 A
F38
Disabled
F58
Block Interval
F16
15 min.
F16
20 min.
F57
None
F86
10.0 MW
F38
Disabled
F58
Block Interval
F16
15 min.
F16
20 min.
F57
None
F86
10.0 Mvar
F38
Disabled
F58
Block Interval
F16
15 min.
F16
20 min.
F57
None
F86
10.0 MVA
F38
Disabled
F57
None
F86
100 MWh
F57
None
F86
100 MWh
F57
None
F86
100 Mvarh
F57
None
F86
100 Mvarh
F33
"ANALOG INPUT"
F33
"µA"
F42
0-20 mA
F1
0
F1
20000
F39
Disabled
F57
None
F1
100
F1
100 s
F85
Over
F1
5%
F39
Disabled
F57
None
F1
100
F1
100 s
4 - 35