GE
Grid Solutions
750/760 Feeder Management Relay
Chapter 5: DNP Communications
DNP 3.0 Device Profile Document
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DNP Communications
The communications port configured as a DNP slave port must support the full set of
features listed in the Level 2 DNP V3.00 Implementation (DNP-L2) described in Chapter 2 of
the subset definitions. See the DNP protocol website at
DNP 3.0: DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Multilin Inc.
Device Name: 750/760 Feeder Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP
Levels Supported (the complete list is described in the attached table):
Binary Input (Object 1, variations 1 and 2)
Binary Output (Object 10, variation 2)
Analog Input (Object 30, variations 1, 2, 3, and 4)
Analog Input Change (Object 32, variations 1, 2, 3, and 4)
Warm Restart (Function Code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Data Link Re-tries:
None
Ë
Fixed
Ë
Configurable (note 1)
http://www.dnp.org
Device Function:
Master
Slave
Ë
Ë
Maximum Application Fragment Size
(octets):
Transmitted: 2048
Received: 2048
Maximum Application Layer Re-tries:
None
Ë
Configurable
Ë
for details