GE 750 Manual page 74

Feeder management relay
Hide thumbs Also See for 750:
Table of Contents

Advertisement

DATA FORMATS
4 - 54
Table 4: Data Formats (Sheet 9 of 20)
Type
Value
101
Simulate Fault
102
Trigger Data Log
3
Block All Sensitive Ground Overcurrent
103
3
Block Sensitive Ground Instantaneous OC
104
3
Block Sensitive Ground Time Overcurrent
105
4
Block Reverse Power (requires Mod 008)
106
4
Block Neutral Displacement
107
7
User Input I
108
7
User Input J
109
7
User Input K
110
7
User Input L
111
7
User Input M
112
7
User Input N
113
7
User Input O
114
7
User Input P
115
7
User Input Q
116
7
User Input R
117
7
User Input S
118
7
User Input T
119
7
Start Demand Interval
120
Self-Test Warning Event Type
00FFh
Event Cause (last 8 bits)
F24
1
Relay Not Ready
ctd.
2
Analog Output +32V
3
FLASH Corrupt
4
EEPROM Corrupt
5
Dry Contact +32V
6
A/D Virtual Ground
7
Internal RS485
8
Internal Temperature
9
Clock Not Set
10
Prototype Software
11
Not Calibrated
12
Force Relays
13
Force Analog Out
14
Simulation Mode
15
Pickup Test
16
Factory Service Mode
17
IRIG-B Failure
7
Not Used
18
7
Not Used
19
7
RTC Crystal
20
50
Self-Test 1
51
Self-Test 2
Maintenance Alert Event Type
00FFh
Event Cause (last 8 bits)
1
Event Rate High
2
EEPROM Usage High
1 2 3 4 5 6 7 8 9 10 11 12 13
For explanation of footnotes, see notes of end of Table.
CHAPTER 4: MODBUS MEMORY MAP
Description
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE

Advertisement

Table of Contents
loading

This manual is also suitable for:

760