GE 750 Manual page 50

Feeder management relay
Hide thumbs Also See for 750:
Table of Contents

Advertisement

MEMORY MAP
Table 3: Modbus Memory Map (Sheet 25 of 40)
ADDR
PHASE INSTANTANEOUS OVERCURRENT 2 (read/write setpoints)
2
Phase Instantaneous Overcurrent 2 Function
1510
2
Phase Instantaneous Overcurrent 2 Relays
1511
2
Phase Instantaneous Overcurrent 2 Pickup
1512
2
Phase Instantaneous Overcurrent 2 Delay
1513
1514
Phases Required for Operation
1
Phase Instantaneous Overcurrent 2 Direction
1515
PHASE DIRECTIONAL OVERCURRENT (read/write setpoints)
1520
Phase Directional Function
1521
Phase Directional Maximum Torque Angle
1
Minimum Polarizing Voltage
1522
1523
Phase Directional Relays
4
Block OC When Voltage Memory Expires
1524
PHASE TIME OVERCURRENT 2 (read/write setpoints)
1
Phase Time Overcurrent 2 Function
1530
1
Phase Time Overcurrent 2 Relays
1531
1
Phase Time Overcurrent 2 Curve
1532
1
Phase Time Overcurrent 2 Voltage Restraint
1533
1
Phase Time Overcurrent 2 Pickup
1534
1
Phase Time Overcurrent 2 Multiplier
1535
1
Phase Time Overcurrent 2 Reset Time
1536
1
Phase Time Overcurrent 2 Direction
1537
GROUND TIME OVERCURRENT (read/write setpoints)
1600
Ground Time Overcurrent Function
1601
Ground Time Overcurrent Relays
1602
Ground Time Overcurrent Curve
1
Ground Time Overcurrent Pickup
1603
1
Ground Time Overcurrent Multiplier
1604
1
Ground Time Overcurrent Reset Time
1605
6
Ground Time Overcurrent Direction
1606
GROUND INSTANTANEOUS OVERCURRENT (read/write setpoints)
2
Ground Instantaneous Overcurrent Function
1608
2
Ground Instantaneous Overcurrent Relays
1609
2
Ground Instantaneous Overcurrent Pickup
160A
2
Ground Instantaneous Overcurrent Delay
160B
6
Ground Instantaneous Overcurrent Direction
160C
GROUND DIRECTIONAL OVERCURRENT (read/write setpoints)
6
Ground Directional Function
160E
6
Ground Directional Maximum Torque Angle
160F
6
Ground Directional Minimum Polarizing Voltage
1610
6
Ground Directional Polarizing
1611
6
Ground Directional Relays
1612
NEUTRAL TIME OVERCURRENT 1 (read/write setpoints)
1630
Neutral Time Overcurrent 1 Function
1631
Neutral Time Overcurrent 1 Relays
1632
Neutral Time Overcurrent 1 Curve
1
Neutral Time Overcurrent 1 Pickup
1633
1 2 3 4 5 6 7 8 9 10 11 12 13
For explanation of Table footnotes, see the Memory Map Notes at the end of this table.
4 - 30
DESCRIPTION
CHAPTER 4: MODBUS MEMORY MAP
RANGE
UNITS
---
---
---
---
0.05 to 20.00
x CT
0.00 to 600.00
s
---
---
---
---
---
---
0 to 359
° Lead
0.00 to 1.25
x VT
---
---
---
---
---
---
---
---
---
---
---
---
0.05 to 20.00
x CT
0.00 to 100.00
---
---
---
---
---
---
---
---
---
---
---
0.05 to 20.00
x CT
0.00 to 100.00
---
---
---
---
---
---
---
---
---
0.05 to 20.00
x CT
0.00 to 600.00
s
---
---
---
---
0 to 359
° Lead
0.00 to 1.25
x VT
---
---
---
---
---
---
---
---
---
---
0.05 to 20.00
x CT
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
TYPE
DEFAULT
F37
Disabled
F57
None
F3
1.00 x CT
F3
0.00 s
F41
Any One
F84
Disabled
F38
Disabled
F1
30° Lead
F3
0.05 x VT
F57
None
F30
Disabled
F37
Disabled
F57
None
F36
Ext. Inverse
F30
Disabled
F3
1.00 x CT
F3
1.00
F68
Instantaneous
F84
Disabled
F37
Disabled
F57
None
F36
Ext. Inverse
F3
1.00 x CT
F3
1.00
F68
Instantaneous
F84
Disabled
F37
Disabled
F57
None
F3
1.00 x CT
F3
0.00 s
F84
Disabled
F38
Disabled
F1
315°
F3
0.05 x VT
F50
Voltage
F57
None
F37
Disabled
F57
None
F36
Ext. Inverse
F3
1.00 x CT

Advertisement

Table of Contents
loading

This manual is also suitable for:

760

Table of Contents