Testing Calibration - Siemens FDUL221 Technical Manual

Line tester
Hide thumbs Also See for FDUL221:
Table of Contents

Advertisement

7
Maintenance / Repair
Testing the line tester
7.1.2
66
Building Technologies
Fire Safety

Testing calibration

If testing manually, use a digital voltmeter with 'True RMS'.
The table below shows the nominal measured value as a function of the configured
control unit.
Control panel
FS20
FS720
CS114x
SIGMASYS
Mode
Nominal measured value
FDnet 32 V
DC 28 V ± 5 %
AC 10 V ± 10 %
FDnet SIGMA
DC 24 V ± 5 %
AC 8 V ± 10 %
008250_i_en_--
2013-08-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents