6.5 Configuring the line tester
50
Building Technologies
Fire Safety
The FDUL221 line tester must be set to the relevant protocol if it is being used on a
detector line. The protocol is permanently set in the 'EL' operation mode and
cannot be configured.
Control panel
Protocol
FC20xx
FDnet
FC72x
C-NET
CS114x
FDnet
SIGMASYS
FDnet
_
FDnet/C-NET
To configure, proceed as follows:
The FDUL221 line tester is switched off.
1. Hold down the
button and switch the FDUL221 line tester on with the
switch.
The FDUL221 line tester is in the 'Configuration' menu tree.
2. Select 'Mode: FDnet ...' using the
3. Select the required protocol with the
4. Select further sub menus or a function with the
5. Further changes in the sub menu or function can be made in the same way.
6. To quit a sub menu or a function, press the
7. To quit 'Configuration', select 'Save & Exit' or 'Exit'.
The FDUL221 line tester switches to the 'Topology' menu tree.
See also
Navigating in the menu tree [
Mode: FDnet
32 V
32 V
32 V
SIGMA
Spy
buttons.
button.
buttons.
button.
40]
008250_i_en_--
2013-08-15