Table Of Faults - Siemens FDUL221 Technical Manual

Line tester
Hide thumbs Also See for FDUL221:
Table of Contents

Advertisement

6
Operation

Table of faults

6.13
Error display
Possible cause
E01 Short
Short-circuit on the detector line. The line separator is open
for the line device shown on the display.
E02 Open (+)
Open line on the
cannot be identified by the FDUL221 line tester.
E03 Open (-)
Open line on the
E04 Hi leak
High leakage current
The typical leakage current is approx. 300 µA (base current)
and approx. 3 µA per line device.
E05 High cap
a) High line capacity
b) Error during migration, e.g. due to forgotten line device
58
Building Technologies
Fire Safety
Table of faults
Below you will find an overview of the errors displayed by the FDUL221 line tester
as well as possible causes and remedies for the errors.
Line device
Line device is shown on the display, the internal and external alarm indicators flash
Position of the line device not detected
Line device is shown on the display with an error
line The exact position of the open line
line
Remedy
Locate the short-circuit by checking the cable
section behind the line device shown on the
display. In the case of a loop, the location is
also shown as an 'open line'.
Check the cable. Search for the faulty location
by disconnecting the detector line and re-
checking the cable connection.
Disconnect the return line and restart the
detector line. The open line is located behind
the last line device shown on the display.
Open the loop at one end and restart the
detector line. The open line is located behind
the last line device shown on the display.
Check the cable insulation.
In the case of migrated detector lines:
Check whether old line devices are still
installed on the detector line.
Check whether EOL elements, e.g.
resistors, are still installed on the detector
line.
Line too long. Reduce the length of the loops
or stubs, e.g. through division.
The maximum line length is 3.3 km for
FS20/FS720, 2.5 km for SIGMASYS and also
depends on the line type.
R
= 240 , C
= 750 nF
lmax
lmax
Replace the affected line device.
008250_i_en_--
2013-08-15