Siemens FDUL221 Technical Manual page 59

Line tester
Hide thumbs Also See for FDUL221:
Table of Contents

Advertisement

Error display
Possible cause
E06 (-) -> EARTH
a)
b) The connection for the external AI is grounded
E07 (+) -> EARTH
be identified by the FDUL221 line tester.
E08 series R
High resistance
E09 More err
The error list is limited to a maximum number of error
messages that can be displayed. However, more errors are
available than can be currently displayed.
E10 >252 dev
There are too many devices on the detector line that has
been read-in. A maximum of 252 devices may be installed
on a FDnet/C-NET detector line.
E11 bad TTap
A sub-stub is not permitted in this location.
Note: This error number indicates several line devices as
faulty.
E12 >2 TTap
Several sub-stubs directly after one another without a line
separator in between are not permitted.
Note: This error number indicates several line devices as
faulty.
Building Technologies
Fire Safety
line is grounded
+
(D)
_
line is grounded. The exact position of the error cannot
?
+
_
Remedy
Search for the ground fault. In particular, note
connections for line devices with grounded
components, shielded cables, etc.
+
_
Find the faulty location by separating the parts
of the detector line and checking the separated
line parts (e.g. ½, ¼,
on 'Error search' [
+
?
_
Resistance in the detector line is too high.
Check the lines and the connection points
(terminals). Ensure that the line is not too long.
+
(D)
Limit values: See error E05
Use the 'Measure Device' menu item.
_
Rectify the errors displayed and then read in
the detector line again. The errors that were
not originally displayed will then be shown.
The read-in loop or stub must be divided into
several loops or stubs with less line devices.
A branch is not allowed. Change the wiring.
Ensure that a 'sub-stub on stub' topology has
not been wired. Only one or several individual
sub-stubs can branch from a loop.
Ensure that there is a line device, e.g. a line
separator, between two sub-stubs branching
off from the loop.
Only one sub-stub may branch off from a loop
between two line devices on the detector line.
Operation
6
Table of faults
). Also refer to the tips
61].
59
008250_i_en_--
2013-08-15