Structure And Function; Overview - Siemens FDUL221 Technical Manual

Line tester
Hide thumbs Also See for FDUL221:
Table of Contents

Advertisement

5

Structure and function

Overview

5 Structure and function
5.1 Overview
20
Building Technologies
Fire Safety
Various functions are available depending on which software is installed: A
comparison of the functions can be found in chapter 'Comparison of software
functions [
15]'.
The line tester FDUL221 serves for system diagnostics on an addressed detector
line.
Reads the line topology
Detects cable errors
Short-circuit
Open line
Ground fault
Resistors
Measures resistances
Shows the arrangement of the line devices on the detector line
Shows the current status of the line devices
Detects errors
Shows the address
Allocates an address in the event of double assignment or missing address
Saves line topologies in 'EL' operation mode
Communicates with the 'PC Linetester Tool FXS2017' software
The FDUL221 line tester is controlled by buttons.
If a line device is connected or removed later, the line topology previously read in is
not updated automatically.
The FDUL221 line tester can be operated independently or with the 'PC Linetester
Tool FXS2017' software.
Features of the FDUL221 line tester
Battery or mains operation
Multi-line display
Backlight
Loadable language variants
Automatic address correction
Clearly arranged operating and indication elements
Save read-in topologies
Generate a report for the read-in topologies
Transfer reports to a connected PC using the 'PC Linetester Tool FXS2017'
software
008250_i_en_--