Trip Log

When the MCD3000 enters a trip state, the cause of
the trip is recorded in a trip log. The trip log records
the cause of the last eight trip events. Each trip event
is numbered. The most recent event is numbered 1,
while the oldest is numbered 8.
ATTENTION
Control voltage must be present to enable the
MCD3000 to record the cause of a trip event.
Therefore, trips caused by, or involving a loss of
control supply voltage may not be recorded.
To view the trip log;
Enter the programming mode and move to Par.
45, Trip Log.
Press the [CHANGE DATA/OK] button to view the
most recent trip.
Use the [+/-] buttons to scroll through the trip log.
A 'marker' can be placed in the trip log to enable easy
identification of trips that have occurred after the
marker has been placed.
To place a marker;
Enter the programming mode and move to Par.
45 Trip Log.
Press the [CHANGE DATA/OK] button to view the
trip log.
While simultaneously holding down the [+], [-]
buttons, press the [CHANGE DATA/OK] button.
The marker is added as the most recent trip and is
displayed as the letter 'A' as shown below.
ATTENTION
Markers cannot be placed consecutively.
There must be at least one trip between each
marker.
General Faults
Symptom
Cause & Action
Starter will
Incorrect or no control supply
not operate.
voltage. Ensure the correct voltage
is applied. (Terminals A1,A2 & A3).
MG.15.A2.22 – VLT is a registered Danfoss trademar
MCD3000 Series
Symptom
Cause & Action
MCD3000 is in programming mode.
Exit the programming mode.
Local push buttons not active. If
attempting to use the start button on
the Local Control Panel, ensure the
MCD3000 is in local control mode.
(Refer to Par. 20 Local/Remote
Mode for details).
Remote inputs not active. If
attempting to use the MCD3000
remote inputs, ensure the MCD3000
is in remote control mode. (Refer to
Par. 20 Local/Remote Mode for
details).
Remote start signal not valid. If
attempting to use the remote start
input on the MCD3000, ensure the
remote contacts are correctly
connected and operating properly.
Do this by observing the remote
control input LEDs. The LEDs
illuminate when there is a closed
circuit. In addition to the start signal
there must be a closed circuit
across the stop and reset inputs for
the starter to function.
Restart delay active. A start cannot
be initiated within the programmed
restart delay period. (Refer to Par.
15 Restart Delay for details).
Auto-Reset active. If there has been
a trip and the Auto-Reset function
has been turned ON, the MCD3000
will be in Auto-Reset mode. This
includes a reset delay period, during
which a start cannot be initiated
without first resetting the starter.
(Refer to Par. 39,40, 41 & 42
Automatic-Reset for details).
Starter will
Starter is running. Stop the starter
not enter
and try again.
program
Incorrect or no control supply
mode.
voltage. Ensure the correct supply
voltage is applied. (Terminals A1,A2
& A3).
Program
Read Only mode is active. Set Par.
settings
48 Parameter Lock to Read/Write.
cannot be
Incorrect programming procedure.
made.
User programmed settings must be
stored using the [CHANGE
43