Danfoss MCD3000 Series Manual page 22

Hide thumbs Also See for MCD3000 Series:
Table of Contents

Advertisement

technique described in the Design Guide section of
this manual.
20
Local / Remote Mode
Value:
0 - 3
0 ([LOCAL/REMOTE] button enabled)
0 = [Local/Remote] push button on MCD3000
enabled all the time.
1 = [Local/Remote] push button on MCD3000
enabled only while motor stopped.
2 = Local control only. (MCD3000 push buttons
enabled, remote inputs disabled)
3 = Remote control only. (MCD3000 push buttons
disabled, remote inputs enabled)
Function:
Determines when MCD3000 push buttons and remote
control inputs are operative. Also when, and if, the
[Local/Remote] push button can be used to switch
between local and remote control.
Description of choice:
Set according to desired operational requirements.
21
Current Gain
Value:
85% - 115%
Function:
Adds a gain to the MCD3000 current monitoring
circuits. These circuits are factory calibrated with an
accuracy of ±5%. The gain can be used to match the
MCD3000 current read out with an external current
monitoring system.
ATTENTION
This adjustment affects all current based
functions. e.g. current read-out, motor
overload & all other current based protections and
current outputs.
Description of choice:
The gain should be adjusted according to the following
formula.
= factory setting
22
MCD3000 Series
22
Serial Communications - Baud Rate
Value:
1 - 5
1 = 1200 baud
2 = 2400 baud
3 = 4800 baud
4 = 9600 baud
5 = 19200 baud
Function:
Sets the baud rate for serial communications.
Description of choice:
Set as appropriate.
23
Serial Communications - Satellite Address
Value:
1 - 99
Function:
100%
Assigns the MCD3000 an address for serial
communications.
Description of choice:
Set a unique address number as appropriate.
24
Serial Communications - RS485 Time Out
Value:
0 - 100 second
Function:
Sets the maximum allowable period of RS485
inactivity.
Description of choice:
Set this parameter if it is required that a trip should
occur in the event of a failure of RS485
communications with the MCD3000.
MG.15.A2.22 – VLT is a registered Danfoss trademark
4 (9600 baud)
20
0 seconds (Off)

Hide quick links:

Advertisement

Table of Contents
loading