Danfoss MCD3000 Series Manual page 42

Hide thumbs Also See for MCD3000 Series:
Table of Contents

Advertisement

Code
Cause & Action
Motor thermistor trip.
3
Thermistors in the motor have indicated
an overtemperature state.
Identify and correct the cause of the
motor overheating.
Wait for the motor to cool
sufficiently to allow a restart.
Reset the MCD3000.
Restart the motor.
If no motor thermistors are connected;
Ensure that there is a closed circuit
across the MCD3000 motor
thermistor input terminals.
Phase imbalance trip.
4
An imbalance in phase currents has
exceeded the limits programmed in Par.
7 Phase Imbalance Sensitivity.
Check the supply voltage.
Verify the motor circuit.
Reset the MCD3000.
Restart the motor.
Check phase currents.
Supply frequency trip.
5
The supply frequency has varied outside
the allowed limits. Refer to Specification
section.
Identify and correct the cause of the
frequency variations. (Note that the
loss of the three phase supply is a
0Hz condition and may be the
cause of a Supply frequency trip).
Reset the MCD3000.
Restart the motor.
Phase rotation trip.
6
Phase rotation protection has been set
and a prohibited phase rotation has
been detected. Refer Par. 11 Phase
Rotation Protection.
Correct the phase rotation.
Reset the MCD3000.
Restart the motor.
Instantaneous overload trip.
7
An instantaneous overload exceeding
the limit programmed in Par. 9
Instantaneous Overload Trip Point has
been detected.
Identify and correct the cause of the
instantaneous overload.
Reset the MCD3000.
Restart the motor.
42
MCD3000 Series
Code
Cause & Action
Power circuit fault.
8
Ensure voltage is present on the
MCD3000 input terminals (L1, L2 &
L3).
Ensure the motor is correctly
connected to the MCD3000 output
terminals (T1, T2 & T3).
Test the MCD3000 power modules
(SCRs) using the SCR Test
described later in this section of the
manual under the Test and
Measurement Procedures heading.
Undercurrent trip.
9
Motor run current has fallen below the
limit programmed in Par. 8 Undercurrent
Trip Point.
Identify and correct the cause of the
undercurrent situation.
Reset the MCD3000.
Restart the motor.
RS485 communications fault
c
The RS485 link with the MCD3000 has
been inactive for a time greater than
programmed in Par. 24 Serial
Communication - RS485 Time Out.
Identify and correct the cause of the
RS485 failure.
Reset the MCD3000.
EEPROM Read/Write failure.
e
The MCD3000 has been unable to
Read/Write to the internal EEPROM.
Contact your nearest Danfoss
office.
Starter overtemperature.
f
An excessive heatsink temperature has
been recorded.
Ensure all cooling fans are working.
Ensure cooling air is able to flow
freely into and out of the starter.
Ensure the temperature of the
cooling air entering the MCD3000
does not exceed the rated
temperature.
Reset and restart the MCD3000
after allowing time for the heatsink
to cool.
MG.15.A2.22 – VLT is a registered Danfoss trademark

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents