Mechanical installation

Models MCD3007~3132 have an IP21 rating and can
be wall mounted or installed inside another enclosure.
These models can be mounted side by side with no
clearance.
Models MCD3185~3800 have an IP20 rating and
must be mounted in another enclosure. These models
must have a clearance of 100mm (4 inches) on either
side.
ATTENTION
Do not mount in direct sunlight or near heat
radiating elements.

Ventilation

MCD3000 cooling is by means of air circulation.
Consequently, the air needs to be able to move freely
above and below the soft starter.
Soft starters dissipate approximately 4.5 watts per
amp. When installing a soft starter in a switchboard or
MG.15.A2.22 – VLT is a registered Danfoss trademar
MCD3000 Series
other enclosure, ensure there is sufficient airflow
through the enclosure to limit heat rise in the
enclosure.
The table below shows airflow requirements for
selected motor currents.
Motor
Heat
Amps
(watts)
10
45
20
90
30
135
40
180
50
225
75
338
100
450
125
563
150
675
175
788
200
900
250
1125
300
1350
350
1575
400
1800
450
2025
500
2250
550
2475
600
2700
ATTENTION
If other heat sources are installed in an
enclosure with the MCD3000, this heat must
also be considered when calculating required airflow.
ATTENTION
If the MCD3000 is installed in an enclosure
without ventilation a bypass contactor should
be employed to prevent heat dissipation during run.
3
Required Airflow m
/min
o
o
o
o
5
C/41
F
10
C/50
F
Rise
Rise
0.5
0.2
0.9
0.5
1.4
0.7
1.8
0.9
2.3
1.1
3.4
1.7
4.5
2.3
5.6
2.8
6.8
3.4
7.9
3.9
9.0
4.5
11.3
5.6
13.5
6.8
15.8
7.9
18.0
9.0
20.3
10.1
22.5
11.3
24.8
12.4
27.0
13.5
7