Guide for Commissioning of ET 200pro with Fail-Safe Modules

Introduction
The following table lists all important steps required for commissioning ET 200pro distributed
I/O systems with fail-safe modules as DP slaves/IO devices on
PROFIBUS DP/PROFINET IO.
Sequence of Steps Starting From Selection of F-Modules to Commissioning of ET 200pro
Table 1-2
Step
1.
2.
3.
4.
5.
6.
7.
Note
You must configure and assign parameters for the F-modules in
commissioning.
Reason:
must set these PROFIsafe addresses on each F-module via a switch before mounting the
module.
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
1.3 Guide for Commissioning of ET 200pro with Fail-Safe Modules
Sequence of Steps Starting From Selection of F-Modules to Commissioning of
ET 200pro
Procedure
Select F-modules for ET 200pro
configuration.
Configure and assign parameters for F-
STEP 7
modules in
.
Set PROFIsafe addresses on F-modules.
Mount ET 200pro.
Wire ET 200pro.
Commission ET 200pro on
PROFIBUS DP/PROFINET IO.
If commissioning was not successful,
perform diagnostics on ET 200pro.
STEP 7
automatically assigns the PROFIsafe addresses to the F-modules. You
See ...
Chapter "Configuration Options"
Chapter "Configuration and Parameter
Assignment" and "Fail-Safe Modules"
Chapter "Address Assignment and
Installation"
Chapter "Address Assignment and
Installation"
Chapter "Wiring and Assembly"
ET 200pro Distributed I/O Device
Chapters "Diagnostics" and "Fail-Safe
ET 200pro Distributed I/O
Modules" and
Device
manual
STEP 7
prior to
Product Overview
manual
17