Siemens SIMATIC Operating Instructions Manual page 72

Distributed i/o fail-safe engineering et 200pro distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Fail-Safe Electronic Modules
8.1 8 /16 F-DI DC24V PROFIsafe Digital Electronic Module
Wiring Diagram for Use Case 2.2 – Connecting Two One-Channel Sensors Via Two Channels
Two single-channel sensors are connected via two channels to two inputs of the F-module
for each process signal (1oo2 evaluation). The sensors can also be supplied via an external
sensor supply.
The figure below illustrates an example wiring diagram for channel groups 1 and 2.
1L+
1L+ M
L+
Figure 8-9
In order to achieve SIL3/Category 3 with this wiring, you must install a suitably qualified
sensor, for example, in accordance with IEC 60947.
Assignable Parameters for Use Case 2.2
Set the "Evaluation of the sensors" parameter to "1oo2 evaluation" and the "Type of sensor
interconnection" parameter to "2-channel equivalent" for the relevant input. Disable the
"Short-circuit test" parameter.
72
Vs1
DI0
S0
M
Wiring Diagram for F-DI Modules - Two One-Channel Sensors Connected Via Two
Channels, Internal Sensor Supply
WARNING
8/16 F-DI
4/8 F-DI/4 F-DO
DI1
DI2
DI3
S1
S2
S3
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
Vs2
DI4
DI5
DI6
DI7