Siemens SIMATIC Operating Instructions Manual page 47

Distributed i/o fail-safe engineering et 200pro distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Testing for Mechanical Environmental Conditions
The following table provides information on the type and scope of tests for mechanical
environmental conditions.
Condition
Test Standard
Vibrations
Vibration test in
accordance with
IEC 60068-2-6
Shock
Shock, tested in
accordance with
IEC 60068-2-27
Repetitive shock
Shock, tested in
accordance with
IEC 60068-29
Reduction of Vibrations
If fail-safe modules are subjected to greater shocks or vibrations, you must take appropriate
measures to reduce acceleration and amplitude.
We recommend that you mount the ET 200pro on damping material (e.g., on a rubber-metal
vibration damper).
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
6.4 Mechanical and Climatic Environmental Conditions
Terminal and Electronic Modules
Type of vibration: Frequency sweeps with a sweep rate of 1
octave/minute.
5 Hz ≤ f ≤ 8 Hz, constant amplitude of 0.75 mm
8 Hz ≤ f ≤ 150 Hz, constant acceleration of 10 g
Duration of vibration: 10 frequency sweeps per axis in each of the
3 perpendicular axes
Type of shock: half sine
Force of shock: 30 g peak value, 18 ms duration
Direction of shock: 3 shocks each in +/- direction in each of the
3 perpendicular axes
Type of shock: half sine
Force of shock: 25 g peak value, 6 ms duration
Direction of shock: 1000 shocks each in +/- direction in each of the three
perpendicular axes
General Technical Specifications