8.1.4

Parameters for the 8/16 F-DI DC24V PROFIsafe Electronic Module

STEP 7
Parameters in
The following table presents the parameters that can be assigned to the 8/16 F-DI DC24V
PROFIsafe electronic module.
Table 8-2
Parameters
F-parameters:
F_destination_addre
ss
F-monitoring time
Module Parameters:
Input delay
Short-circuit test
Behavior after
channel faults*
Channel n, n+4
Evaluation of the
sensors
Type of sensor
interconnection
Behavior at
discrepancy
Discrepancy time
Reintegration after
discrepancy error
* This setting is only relevant when the S7 Distributed Safety V 5.4 or higher optional package is
installed.
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
8.1 8 /16 F-DI DC24V PROFIsafe Digital Electronic Module
Parameters for the 8/16 F-DI DC24V PROFIsafe Electronic Module
Range
1 to 1022
10 to 10000 ms
0.5; 3; 15 ms
Cyclic/Disable
Passivate the entire
module/Passivate the
channel
Enabled/disabled
1oo2 evaluation/
1oo1 evaluation
1-channel;
2-channel equivalent;
2-channel nonequivalent
Provide last valid value;
Provide value 0
10 to 30000 ms
Test of 0-signal not
required/Test of 0-signal
required
Fail-Safe Electronic Modules
Default
STEP 7
Assigned by
150 ms
3 ms
Cyclic
Passivate the entire
module
Enabled
1oo2 evaluation
2-channel equivalent
Provide last valid value
10 ms
Test of 0-signal not
required
Type of
Range of
parameter
effectiven
ess
Static
Module
Static
Module
Static
Module
Static
Module
Static
Module
Static
Channel
group
Static
Channel
group
Static
Channel
group
Static
Channel
group
Static
Channel
group
Static
Channel
group