Wiring Diagram for Use Case 2.1 – Connecting One Sensor Via One Channel to Two Inputs
One sensor is connected via one channel to two inputs of the F-module for each process
signal (1oo2 evaluation).
The wiring is carried out at the appropriate connection module.
In order to achieve SIL3/Category 3 with this wiring, you must install a suitably qualified
sensor, for example, in accordance with IEC 60947.
Note
If the voltage is supplied to the sensor from the F-Switch PROFIsafe electronic module, you
must use the internal sensor supply Vs1. Connection to Vs2 is not possible.