Terminal Assignment Of The F-Switch Profisafe Electronic Module - Siemens SIMATIC Operating Instructions Manual

Distributed i/o fail-safe engineering et 200pro distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Fail-Safe Electronic Modules
8.3 F -Switch PROFIsafe Digital Electronic Module
8.3.2

Terminal Assignment of the F-Switch PROFIsafe Electronic Module

Terminal Assignment on CM F-IO 2xM12 Connection Module
The following table contains the terminal assignment of the F-Switch PROFIsafe on the CM
F-IO 2xM12 connection module.
Sockets X1 to X2 are assigned twice. This enables you to implement a 1oo2 evaluation with
one connecting cable, e.g., channels 0 and 2 at connector X1.
The functional ground (FG) is located on the shield.
Table 8-20
Terminal Assignment on CM F-IO 2×M12 Connection Module for F-Switch PROFIsafe
Circular connector view
3-, 4- or 5-core copper cable
1
Provided by the ET 200pro for the connected sensor
2
108
Terminal
Assignment of X1 to X2
1
Connectors X1 to X2: 24 V sensor supply 1 (Vs1)
2
Input signal:
Connector X1: Channel 2
Connector X2: Channel 3
3
Sensor supply ground (1M)
4
Input signal:
Connector X1: Channel 0
Connector X2: Channel 1
5
Connectors X1 to X2: 24 V sensor supply 2 (Vs2)
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
2
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents