Distributed i/o fail-safe engineering et 200pro distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Data for Selecting a Sensor **
Input current
Input delay
Input characteristic
Connection of 2-wire BERO
Data for Selecting an Actuator**
Output voltage
Output current for "1" signal
For "0" signal (residual current)
Indirect control of load by means of coupling
relay:
For "0" signal (residual current)
Load resistance range
Lamp load
Wire break monitoring (open load detection) and
overload monitoring
Parallel switching of 2 outputs
Control of a digital input
Switching frequency
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
8.2 4 /8 F-DI/4 F-DO DC24V/2A PROFIsafe Digital Electronic Module
Input voltage
Rated value
"1" signal
"0" signal
"1" signal
For "0" after "1"
For "1" after "0"
Permissible quiescent current
"1" signal
Rated value
Permissible range
P-switch
M-switch
Response threshold
Fault detection time
With resistive load
With inductive load in accordance with IEC
60947-5-1, DC13
With lamp load
Technical Specifications
24 V DC
15 V to 30 V
-30 V to 5 V
Typ. 3.7 mA
Assignable (for all inputs together)
Typ. 0.5 ms
Typ. 3 ms
Typ. 15 ms
Typ. 0.5 ms
Typ. 3 ms
Typ. 15 ms
In accordance with IEC 61131-2, Type 1
Not possible
Max. 0.6 mA
Min. L+ (-1.5 V)
P-switch: L+ (-1.5 V), minimum; voltage drop
at M-switch: 0.5 V, maximum
2 A
20 mA to 2.4 A
Max. 0.5 mA
Max. 0.5 mA
Max. 1 mA
12 Ω to 1 kΩ
Max. 10 W
I < 4 to 19 mA
Depends on the assigned readback time (see
"Response Times"
Not possible
Not possible
Max. 30 Hz
Max. 0.1 Hz
Max. 10 Hz
Fail-Safe Electronic Modules
(0.3 ms to 0.7 ms)
(2.6 ms to 3.4 ms)
(13 ms to 17 ms)
(0.3 ms to 0.7 ms)
(2.6 ms to 3.4 ms)
(13 ms to 17 ms)
)
105