Table 3-6. Power Cable Conduit Recommendations For The Eaton 93Pm-50-1 - Eaton 93PM Installation And Operation Manual

Emergency lighting ups 20–40 kw (480v four wire – ul 924)
Table of Contents

Advertisement

Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-6 for conduit
recommendations.
Per NEC article 300, 3(B), all three-phase conductors must be run in the same conduit. A ground wire must be
run in the same conduit as the phase conductors.
When running parallel wires in multiple conduits a ground wire must be run in each conduit in accordance with
NEC Table 250.122.
Conduit is sized to accommodate neutral conductors the same size as the phase conductor. If an oversized
neutral conductor is to be installed, check the conduit size needed to accommodate the oversized neutral and
use that conduit in place of the conduit listed in Table 3-6.
Conduit is sized to accommodate one ground conductor per conduit, sized in accordance with
NEC Table 250.122.
Conduit sizes listed are for copper wiring only.

Table 3-6. Power Cable Conduit Recommendations for the Eaton 93PM-50-1

UPS Model
UPS Rating
Eaton 93PM-50-1
Eaton 93PM-50-1
Eaton 93PM-50-1
NOTE
Wires per conduit include neutral and ground wire.
Eaton 93PM Emergency Lighting UPS (20–40 kW, 480V Four Wire – UL 924) Installation and Operation Manual P-164000569—Rev 2
Voltage
480 Vac
20 kW
DC
480 Vac
30 kW
DC
480 Vac
40 kW
DC
Terminal
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to UPS Bypass
(A, B, C, Neutral, Ground)
AC Output
(A, B, C, Neutral, Ground)
Battery
(Positive, Negative, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
AC Output
(A, B, C, Neutral, Ground)
Battery
(Positive, Negative, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
AC Output
(A, B, C, Neutral, Ground)
Battery
(Positive, Negative, Ground)
UPS Installation Plan and Unpacking
Minimum Conduit
Number of Wires
Trade Size
in Conduit
(inches)
4
1"
5
1-1/4"
5
1"
3
1-1/2"
4
1-1/4"
5
1-1/4"
5
1-1/4"
3
1-1/2"
4
1-1/4"
5
1-1/4"
5
1-1/4"
3
1-1/2"
www.eaton.com/powerquality
Number of
Conduits
1
1
1
2
1
1
1
2
1
1
1
2
3-15