4 How to Programme
4
[0] *
Normal operation
[1]
Control card test
[2]
Initialisation
[3]
Boot mode
14-50 RFI Filter
Option:
[0]
Off
[1] *
On
15-43 Software Version
Range:
0 N/A*
[0 - 0 N/A]
62
Select
Initialization
[2] to reset all parameter values to default settings, except for par. 15-03
Up's
, par. 15-04
Over Temp's
, and par. 15-05
the next power-up.
Operation Mode
par. 14-22
will also revert to the default setting
Function:
Off
Select
[0] only if the frequency converter is fed by an isolated mains source, i.e. from a special
IT mains source.
In this mode, the internal RFI filter capacitors between chassis and the mains RFI filter circuit are
cut-out to avoid damage of the intermediate circuit and to reduce the ground capacity currents
according to IEC 61800-3.
On
Select
[1] to ensure that the frequency converter complies with EMC standards.
Function:
View the combined SW version (or 'package version') consisting of power SW and control SW.
MG.33.AC.02 - VLT is a registered Danfoss trademark
®