Parameter 37: Manual Turnoff Of Sounder - Honeywell FBII CP-220A Hookup And Installation Instructions

Central station receiver
Table of Contents

Advertisement

REMEMBER!
To leave the Programming
Mode at any time, press
the Esc key. Doing so will
return the CP-220A to its
normal operating mode.
Programming changes will
be stored automatically.
PARAMETER 37:
Manual Turnoff
of Sounder
Page 2-38 Section 2: Programming the CP-220A CP-220A Central Station Receiver
Advancing to Next Parameter:
After programming PARAMETER 36, press the N key to advance to
PARAMETER 37 – the next parameter in Category A.
The CP-220A displays the parameter just programmed ([PARAMETER
NUMBER 36]) with its first digit flashing, indicating its request for the next
parameter number.
You can reach PARAMETER 37 in one of several ways. Press either:
• 3 then 7 , or
then 7 , or
• the
NOTE: When the
immediately – not its number.
MANUAL SOUNDER OFF
Background:
PARAMETER 37 is an adjunct to PARAMETER 04 (see page 2-9), which
was used to globally enable or disable the CP-220A's Internal Sounder. This
sounder calls the operator's attention to an incoming data transmission or to
an error message. If it's enabled (in PARAMETER 04), and the CP-220A is
being operated in the MANUAL Mode (see page 2-103), the sounder will
function according to how PARAMETER 37 is programmed.
In the MANUAL mode, each message received by the unit is stored in a
buffer and then routed to the display each time the NEXT key is pressed. It
is therefore possible for several messages to be held "in memory" until
they're actually displayed.
If this parameter is set for [MANUAL SOUNDER OFF] (the default), each
new message will cause a 2-second beep to occur, alerting the operator who
may otherwise be occupied. If set to [MANUAL SOUNDER ON], the beep
will sound continuously, under the same circumstances, until the NEXT key
is pressed. If other messages are "in waiting," the beep will once again sound
continuously while the process is repeated, until all alarms have been
displayed.
NOTE 1: Regardless of how the parameter is set, all incoming messages will
be sent to an attached printer as they occur, even if they remain
in the display buffer.
key
is used, the name of the next parameter appears
Hook-Up and Installation Manual
M/DD/YY HH:MM:SS

Hide quick links:

Advertisement

Table of Contents
loading