2.2 Installation Requirements

2.2.1
2-2
Place the meter run in service and monitor with ROCLINK 800
software for proper operation.
Careful planning helps to ensure a smooth installation. Be sure to
consider location, ground conditions, climate, and site accessibility, as
well as the suitability of the FB100-Series application while planning an
installation.
The versatility of the FB100 enables you to use it in many types of
installations. For additional information concerning a specific
installation, contact your local sales representative.
: The FB100 has been tested and been found to comply with the
Note
limits for a Class A digital device, pursuant to part 15 of the
FCC rules. These limits provide reasonable protection against
harmful interference when the equipment operates in a
commercial environment. This equipment generates, uses, and
can radiate radio frequency energy. If not installed and used in
accordance with this instruction manual, the FB100 may cause
harmful interference to radio communications. Operation of the
equipment in a residential area is likely to cause harmful
interference, in which case you will be required to correct the
interference at your own expense.

Environmental Requirements

The FB100 enclosure is classified as a NEMA 4 equivalent enclosure.
This provides the level of protection required to keep the units operating
under a variety of weather conditions.
The FB100 is designed to operate over a wide range of temperatures.
However, in extreme climates it may be necessary to moderate the
temperature in which the unit must operate.
The FB100 is designed to operate over a –40°C to +75°C (–40°F to
+167°F) temperature range. The LCD temperature range is –25°C to
+70°C (–13°F to +158°F). When mounting the FB100, be aware of
external devices that could have an effect on the operating temperature.
Operation beyond the recommended temperature range could cause
errors and erratic performance. Prolonged operation under extreme
conditions could also result in failure of the unit.
Check the installation for mechanical vibration. Do not expose the
FB100 to levels of vibration that exceed 2g for 15 to 150 Hz and 1g for
150 to 2000 Hz.
Installation and Use
Revised August-2017