4.4 Analog Output

4.4.1 Wiring the Analog Output (6-point I/O Board)

4-4
Figure 4-2. Analog Input Wiring
The Analog Output (AO) on the 6-point I/O termination board provides
a 4–20 mA current source. The analog outputs use a 12-bit D/A
converter with A/D values of 0 and 4095.
: The switch for the selectable Analog Output/Discrete Output
Note
should be in the AO position, when configured for use as an

Analog Output.

The Analog Output (AO) on the older 4-point I/O termination board
provides either a 1–5 volt signal or a 4–20 mA current control. The
analog outputs use an 8-bit D/A converter with A/D values of 0 and
250. The AO is located at Point Number B2.
Figure 4-3 shows wiring for the Analog Output, where:
AO+ Positive
AO-
Common
Figure 4-3. Analog Output Wiring for 6-point I/O Board
Input/Output
Revised August-2017