Chapter 8 – Calibration
In This Chapter
8.1 Calibration (AI, RTD & Meter)

8.2 Performing a Calibration

Revised August-2017
8.1
Calibration (AI, RTD & Meter) .......................................................... 8-1
8.2
Performing a Calibration .................................................................. 8-1
8.3
Adjusting for Zero Shift .................................................................... 8-7
8.4
Verifying a Calibration ...................................................................... 8-8
This chapter describes the processes for calibrating the AI, RTD, and
Meter modules for the FB100-Series devices.
Use ROCLINK 800 software to perform initial calibration or re-
calibration, which might be required for example after you change an
orifice plate in the meter run handled by the FB103.
The calibration routines support 5-point calibration, with the three mid-
points calibrated in any order. Calibrate the low-end (or zero) reading
first, followed by the high-end (or full-scale) reading. Calibrate the three
mid-points next, if desired.
The diagnostic analog inputs for logic voltage E1, battery voltage E2,
and board/battery temperature E5 are not designed to be calibrated. The
diagnostic analog input for charge input can be resealed and calibrated.
The built-in inputs may be calibrated with the 5-point routine. The built-
in inputs are assigned to the first three analog input points:
Differential pressure (for AGA3) or Meter pressure (for AGA7)
located at AI Point A1.
Static pressure (for AGA3) or Auxiliary pressure (for AGA7)
located at AI Point A2.
RTD temperature located at AI Point A3.
You can then calibrate the optional analog inputs on the termination
board (if you have configured the as analog inputs) using the 5 point
routine.
To perform a calibration:
1.
Start ROCLINK 800 and connect to the FB100.
2.
Select either Meter > Calibration or Configure > I/O > Analog
Input > AI Calibration tab. The Meter Calibration screen displays.
Calibration