Making Process Connections; Configuring The Pulse Interface Module - Emerson FloBoss 103 Instruction Manual

Hide thumbs Also See for FloBoss 103:
Table of Contents

Advertisement

7.1.1 Making Process Connections

Caution

7.1.2 Configuring the Pulse Interface Module

Revised August-2017
The pressure transducers provide the measurement of the line pressure
(P1) and can optionally measure downstream pressure or station inlet
pressure (aux P2).
The Pulse Interface module is attached to the base of the FB104 at the
factory. Due to cable connections between the interface and the FB104
backplane, do not attempt to remove the FB104 from the Pulse Interface
module.
The Pulse Interface module mounts between the bottom of the FB104
and the top of the rotary meter or turbine meter. Refer to Chapter 2 for
mounting instructions.
: The Pulse Interface module is not equipped to provide a
Note
temperature input to the FB104 for gas compensations in AGA7
calculations. This input should come directly into the FB104
through the RTD input on the termination board.
Piping from the meter run connects to the pressure transducers of the
Pulse Interface module. Both the line and auxiliary pressures pipe to
female ¼-18 NPT connections on the sides of the module.
Take care when removing gas lines from the sensor housing. Use
one wrench to hold the sensor stationary while using a second
wrench to remove the gas line. Do not allow the sensor to rotate;
any rotation will damage the sensor's internal wiring.
Use ROCLINK 800 configuration software to configure the Pulse
Interface module. Refer to the ROCLINK 800 Configuration Software
User Manual (Part D301159X012) for instructions on configuring the
meter, the analog inputs, the pulse inputs, and any other parameters for
your application.
The defaults contained within the sensor are the initial pressures read.
You can re-range each sensor through the calibration routines.
Pulse Interface Module
FloBoss 103/104 Instruction Manual
7-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Floboss 104

Table of Contents