Relays

Repeaters

15
16
17
18
XC5010C
XC5010C
XC6010
Honeywell Relay:
Part Number
Impedance
Nominal voltage
DC Pull-In voltage
DC Current
Further relays:
Each repeater extends the bus length by the amount of the single bus length. The
table below summarizes the number of repeaters allowed. Note that the maximum
length depends on the cable specification as described under the cables chapter.
Table 13. Max. baud rate in relation to cable length and no. of repeaters
max. no. of
max. baud rate
repeaters
76.8 Kbaud
5
The repeater is available either with or without a housing. The ordering information
is as follows:
Table 14. Ordering information for repeater
description
repeater without housing
repeater with housing
45
EXCEL 100C INSTALLATION INSTRUCTIONS
15
15
16
16
17
17
18
18
XC5010C
XC6010
XC6010
14500087004
500 Ω
12 V
9 V
20 mA / 10 V
MU1S, MUS1C, RIBU1S, RIBU1C, R7600
resulting max. bus length
(depends upon cable specifications)
7,200 m (24,000 ft.)